Operation

Figure 23 Present status report screens, SCC (above) and module

PRESENT STATUS

MODULE-0

01/12/98

14:06:26

FRAME 35

 

ORDER - 000000 SITE ID - 00000

SITE TAG - 0000000

 

 

 

 

 

**** ACTIVE ALARMS **** Batt Discharging

 

 

 

 

 

 

 

 

 

 

 

A

B

C

DC

LOAD

HERTZ

TIME

 

OUTPUT VOLTS

480

480

480

 

 

 

 

 

 

 

 

OUTPUT AMPS

325

325

325

 

 

 

60.0

 

 

 

OUTPUT FREQUENCY

 

 

 

 

 

 

 

 

LOAD KVA

 

 

 

 

270

 

 

0:06

 

 

BYPASS VOLTS

0

0

0

 

 

 

 

 

 

 

 

END OF REPORT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SELECT : EXIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SCC Status Report

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESENT STATUS

 

MODULE-0

01/12/98

14:06:26

FRAME 35

 

ORDER - 000000

SITE ID - 00000

SITE TAG - 0000000

 

 

 

 

 

**** ACTIVE ALARMS **** Batt Discharging

 

 

 

 

 

 

 

 

 

 

 

A

B

C

DC

LOAD

HERTZ

TIME

 

OUTPUT VOLTS

480

480

480

 

 

 

 

 

 

 

OUTPUT AMPS

325

325

325

 

 

60.0

 

 

 

OUTPUT FREQUENCY

 

 

480

 

 

 

 

 

BATTERY VOLTS

 

 

 

 

 

 

 

0:09

 

 

BATTERY AMPS

 

 

 

-645

 

 

 

 

 

 

 

INPUT VOLTS

0

0

0

 

 

 

 

 

 

 

 

INPUT AMPS

0

0

0

 

270

 

 

 

 

 

LOAD KVA

 

 

 

 

 

 

 

 

 

END OF REPORT

SELECT : EXIT

Module Status Report

Event History

The Event History screen lists the active alarms present in the UPS system (SCC) or modules. This screen also displays the prior 128 alarm frames, in a first in, first out (FIFO) sequence, that have taken place along with the date and the time that each alarm frame occurred. Use the Up and Down pads to look through the different alarm frames.

Figure 24 Event history report screen

EVENT HISTORY

MODULE-0

01/17/98 15:06:41 FRAME 175

ORDER - 000000

SITE ID - 00000

SITE TAG - 0000000

**** ACTIVE ALARMS **** Batt Discharging Low Batt Warning

UP : NEXT FRAME

DOWN : PREVIOUS FRAME

SELECT : EXIT

39

Page 45
Image 45
Liebert 1000kVA manual Event History, SCC Status Report, Module Status Report