Operation
91
3.4.3 Load Transfer Procedures
Use the Monitor/Mimic Display at the SCC to determine the operating condition of the UPS system.
Press the Alarm Reset pad to clear the Alarm Messages. If all UPS modules are on-line, the only
message remaining should be Load On Bypass. Refer to Table 9 for an explanation of any other
remaining alarm messages. Call Liebert Global Services if you cannot clear any remaining alarm
messages.
If the only alarm message displayed is Load On Bypass (or no alarms), you can perform a manual
transfer of the load between the UPS system and the UPS bypass line. Changing the load from the
UPS system to the UPS bypass is called a transfer. Changing the load from UPS bypass to the UPS
system is called a retransfer. Note that the UPS system control logic can initiate automatic load
transfers and retransfers. Refer to 3.5 - Automatic Operations.
Press the Select pad to display the Master Menu on the LCD of the SCC. Move the highlighted cursor
to Load Transfer Procedures (using the Up and Down pads). Press the Select pad to display the
Load Transfer Procedures screen.
Step 1. Verify that the OK TO TRANSFER message is highlighted. If not (if the TRANSFER PRO-
HIBIT message is highlighted instead), slowly rotate the Voltage Adjust knob (Figure 10, item 6)
to match the UPS system voltage to the bypass voltage.
Figure 66 Load transfer procedures screen
Step 2. Perform Step 2 on the Load Transfer Procedures Screen.
a. If the load is on internal bypass, simultaneously press the UPS and Control Enable
pads (Figure 10). This will close the motorized UPS Output circuit breaker and open the
motorized System Bypass circuit breaker (SBB) in a make-before-break sequence.
b. If the load is on the UPS system, simultaneously press the Bypass and Control Enable
pads (Figure 10). This will close the motorized System Bypass circuit breaker (SBB) and
open the motorized UPS Output circuit breaker in a make-before-break sequence.
Return to the Monitor/Mimic Display screen to monitor the operation of the UPS system. Press the
Alarm Reset pad to clear any latched alarm messages removed by the new load status. Refer to
Table 9 if an alarm message other than Load On Bypass is still displayed. Contact Liebert Global
Services if you require assistance.
NOTE
1. UPS output voltage changes VERY slowly in response to movements of the Voltage Adjust
knob. To avoid overshooting, allow at least a minute for UPS output voltage to stabilize
before proceeding to the next step.
2. If the TRANSFER PROHIBIT message remains, refer to Table9 for corrective action for
any alarm messages. Call Liebert Global Services if you cannot solve the problem.
TRANSFERPROHIBIT
UPS LEAD = 2Deg
UPS -
BYPASS -
380380
380381
B-CA-B
VOLTAGECOMPARISON
SELECT : MASTERMENU
OK TO TRANSFER
+30
ONUPS
50.0Hz
379
C-A FREQUENCY
MANUAL
TRANSFERINSTRUCTIONS
1. Adjustthe UPS voltage until it equals the
bypassvoltage with the VOLTAGE ADJUST pot.
2. Ifthe OK TO TRANSFER message is highlighted,
simultaneouslypress the BYPASS andCONTROL ENABLE
buttons.
3. Verifythatthe transfer was successful by checking the
breakerstatus on the "MONITOR/MIMIC" screen.
4. Pressthe ALARM RESET button to clear alarms which
areno longer active
SYNCHRONIZATION
50.0Hz
0-30
380
ON BYPASS
Adjust the UPS voltage until it equals the
bypass voltage with the VOLTAGE ADJUST pot.
If the OK TO TRANSFER message is highlighted,
simultaneously press the UPS and CONTROL ENABLE
buttons.
Verify that the transfer was successful by checking the
breaker status on the "MONITOR/MIMIC" screen.
Press the ALARM RESET button to clear alarms which
are no longer active.