Operation
40
History Status

The History Status screen displays 64 frames, of 4 milliseconds each, from the Present Status screen.

Note that the values for output volts and amps are updated once each millisecond. Alarms are listed

in the sequence they occurred, within 1 millisecond resolution. The frames are stored in a buffer (a

computer information storage technique). The buffer stores the frames in a first in, first out sequence.

As a new frame enters the buffer the oldest one is released.

When a designated fault occurs (see list below), the buffer stores information for the next 24 frames

and then freezes (stops gathering information). At that time, the History Status screen contains

40 frames before the fault, the frame when the fault occurred and 23 frames after the fault. This

64-page report is a very useful diagnostic tool for the operator or Liebert Global Services. Use the Up

and Down pads to view the screens.

Figure 25 History status report screens

OUTPUTVOLTS

OUTPUTAMPS

OUTPUTFREQUENCY

LOADKVA

BYPASSVOLTS

A

480
420
480

DC

B

480
420
480

TIMELOAD

349

C

480
420
480

HERTZ

60.0

NEXTFRAME
PREVIOUSFRAME
EXIT
UP :
DOWN :
SELECT :

HISTORY STATUS MODULE-0 04/10/97 16:49:21 FRAME 36

ORDER- 000000 SITE ID - 00000 SITETAG - 0000000

****ACTIVE ALARMS **** Output Ov-volts

OUTPUTVOLTS
OUTPUTAMPS
OUTPUTFREQUENCY
LOADKVA
BYPASSVOLTS
A
380
530
380
DC
B
380
530
380
TIMELOAD
349
C
380
530
380
HERTZ
50.0
NEXTFRAME
PREVIOUSFRAME
EXIT
UP :
DOWN :
SELECT :
HISTORY STATUS MODULE-0 04/10/97 16:49:21 FRAME 36
ORDER- 000000 SITE ID - 00000 SITE TAG- 00000 00
****ACTIVE ALARMS **** Output Ov-volts
OUTPUTVOLTS
OUTPUTAMPS
OUTPUTFREQUENCY
OUTPUTVOLTS
OUTPUTAMPS
BATTERYVOLTS
OUTPUTVOLTS
OUPUTAMPS
BATTERYAMPS
INPUTVOLTS
INPUTAMPS
OUPUTVOLTS
OUTPUTAMPS
LOADKVA
A
480
325
480
325
480
325
0
0
480
325
DC
390
-645
B
480
325
480
325
480
325
0
0
480
325
TIME
0:01
LOAD
270
C
480
325
480
325
480
325
0
0
480
325
HERTZ
60.0
NEXTFRAME
PREVIOUSFRAME
EXIT
UP :
DOWN :
SELECT :
HISTORY STATUS MODULE-0 01/17/98 11:21:59 FRAME100
ORDER- 000000 SITE ID - 00000 SITE TAG- 00000 00
****ACTIVE ALARMS **** Batt Discharging LowBatt Warning