SEQUENCE OF OPERATION

548J

Cooling, unit without economizer

When thermostat calls for cooling, terminals G and Y1 are energized. The indoor-fan contactor (IFC), reversing valve solenoid (RVS) and compressor contactor are energized and indoor-fan motor, compressor, and outdoor fan starts. The outdoor fan motor runs continuously while unit is cooling.

Heating, unit without economizer

Upon a request for heating from the space thermostat, terminal W1 will be energized with 24V. The IFC, outdoor-fan contactor (OFC), C1, and C2 will be energized. The indoor fan, outdoor fans, and compressor no. 1, and compressor no. 2 are energized and reversing valves are deenergized and switch position.

If the space temperature continues to fall while W1 is energized, W2 will be energized with 24V, and the heater contactor(s) (HC) will be energized, which will energize the electric heater(s).

When the space thermostat is satisfied, W2 will be deenergized first, and the electric heater(s) will be deenergized.

Upon a further rise in space temperature, W1 will be deenergized.

Cooling, unit with EconoMi$er IV

When free cooling is not available, the compressors will be controlled by the zone thermostat. When free cooling is available, the outdoor-air damper is modulated by the EconoMi$er IV control to provide a 50 to 55_F (10_ to 13_C) mixed-air temperature into the zone. As the mixed-air temperature fluctuates above 55 or below 50_F (13_ to 10_C), the dampers will be modulated (open or close) to bring the mixed-air temperature back within control.

If mechanical cooling is utilized with free cooling, the outdoor-air damper will maintain its current position at the time the compressor is started. If the increase in cooling capacity causes the mixed-air temperature to drop below 45_F (7_C), then the outdoor-air damper position will be decreased to the minimum position. If the mixed-air temperature continues to fall, the outdoor-air damper will close. Control returns to normal once the mixed-air temperature rises above 48_F (9_C).

If optional power exhaust is installed, as the outdoor-air damper opens and closes, the power exhaust fans will be energized and deenergized.

If field-installed accessory CO2 sensors are connected to the EconoMi$er IV control, a demand controlled ventilation strategy will begin to operate. As the CO2 level in the zone increases above the CO2 setpoint, the minimum position of the damper will be increased proportionally. As the CO2 level decreases because of the increase in fresh air, the outdoor-air damper will be proportionally closed.

For EconoMi$er IV operation, there must be a thermostat call for the fan (G). If the unit is occupied and the fan is on, the damper will operate at minimum position. Otherwise, the damper will be closed.

When the EconoMi$er IV control is in the occupied mode and a call for cooling exists (Y1 on the thermostat), the control will first check for indoor fan operation. If the fan is not on, then cooling will not be activated. If the fan is on, then the control will open the EconoMi$er IV damper to the minimum position.

On the initial power to the EconoMi$er IV control, it will take the damper up to 21/2 minutes before it begins to position itself. Any change in damper position will take up to 30 seconds to initiate. Damper movement from full closed to full open (or vice versa) will take between 11/2 and 21/2 minutes.

If free cooling can be used as determined from the appropriate changeover command (switch, dry bulb, enthalpy curve, differential dry bulb, or differential enthalpy), then the control will modulate the dampers open to maintain the mixed-air temperature setpoint at 50_ to 55_F (10_ to 13_C).

If there is a further demand for cooling (cooling second stage — Y2 is energized), then the control will bring on compressor stage 1 to maintain the mixed-air temperature setpoint. The EconoMi$er IV damper will be open at maximum position. EconoMi$er IV operation is limited to a single compressor.

Heating, unit with EconoMi$er

When the room temperature calls for heat through terminal W1, the indoor (evaporator) fan contactor (IFC) and heater contactor no. 1 (HC1) are energized and the reversing valve(s) deenergize and switches position. On units equipped for 2 stages of heat, when additional heat is needed, heater contactor no. 2 is energized through W2. The economizer damper moves to the minimum position. When the thermostat is satisfied, the damper moves to the fully closed position.

Defrost

When the temperature of the outdoor coil drops below 28_F (-2_C) as sensed by the defrost thermostat (DFT2) and the defrost timer is at the end of a timed period (adjustable at 30, 60, 90 or 120 minutes), reversing valve solenoids (RVS1 and RVS2) are energized and the OFC is deenergized. This switches the position of the reversing valves and shuts off the outdoor fan. The electric heaters (if installed) will be energized.

The unit continues to defrost until the coil temperature as measured by DFT2 reaches 65_F (18_C), or the duration of defrost cycle completes a 10-minute period.

During the Defrost mode, if circuit 1 defrosts first, RVS1 will oscillate between Heating and Cooling modes until the Defrost mode is complete.

66

Page 66
Image 66
Bryant 548J manual Sequence of Operation

548J specifications

The Bryant 548J is a high-efficiency gas furnace that combines advanced features and technologies to provide exceptional heating performance. Designed for residential applications, the furnace is notable for its ability to deliver consistent warmth while ensuring energy efficiency and reliability.

One of the main features of the Bryant 548J is its ultra-high efficiency rating, which allows homeowners to save significantly on energy costs. With an Annual Fuel Utilization Efficiency (AFUE) rating of up to 96.5%, this furnace is designed to convert a large portion of fuel into usable heat. This is a remarkable characteristic that not only reduces utility bills but also contributes to a lower environmental footprint.

The 548J is equipped with a modulating gas valve and a variable-speed blower motor. The modulating gas valve enables the furnace to adjust its heating output based on real-time temperature demands, ensuring a more precise heating experience. This results in reduced temperature fluctuations within the home, providing a comfortable living environment. The variable-speed blower motor works in tandem with the modulating valve, facilitating improved air circulation and efficient temperature control.

Additionally, the Bryant 548J features a durable and compact design, making it suitable for various installation spaces. Its quality construction ensures longevity, while the optional stainless steel heat exchanger enhances its reliability. The furnace also includes a quiet operation mode, which minimizes noise levels, ensuring that the unit works quietly in the background without disturbing the household's peace.

Integration with smart home technology is another advantage of the Bryant 548J. Homeowners have the option to connect the furnace to a Wi-Fi-enabled thermostat, allowing for remote temperature control and monitoring. This feature offers enhanced convenience and the ability to optimize energy use according to a homeowner’s schedule.

For peace of mind, the Bryant 548J comes with a range of warranties, protecting the consumer's investment. Bryant’s commitment to quality is reflected in their extensive primary heating testing procedures, which ensure that each unit meets strict performance criteria before it reaches the customer.

In summary, the Bryant 548J is an efficient and reliable gas furnace that embodies advanced heating technology. With features such as high AFUE ratings, modulating gas valves, variable-speed blowers, and smart home compatibility, it stands out as a formidable option for modern residential heating solutions.