![23 09 93 Sequence of Operations for HVAC Controls](/images/new-backgrounds/34046/34046137x1.webp)
7.Shall have an LED display independently showing the status of serial communication, running, errors, power, all digital outputs, and all analog inputs.
8.Shall accept the following inputs: space temperature, setpoint adjustment, outdoor air temperature, indoor air qu- ality, outdoor air quality, compressor
9.Shall provide the following outputs: economizer, fan, cooling stage 1, cooling stage 2, heat stage 1, heat stage 2, heat stage 3/ exhaust/ reversing valve.
10.Shall have
11.Shall have a battery
12.Shall have
13.Shall include an
14.Software upgrades will be accomplished by either local or remote download. No software upgrades through chip replacements are allowed.
23 09 33 Electric and Electronic Control System for HVAC
23 09 33.13 Decentralized, Rooftop Units:
23 09 33.13.A. General:
1.Shall be complete with
2.Shall utilize
3.Shall include a central control terminal board to conveniently and safely provide connection points for vital con- trol functions such as: smoke detectors, phase monitor, economizer, thermostat, DDC control options, loss of charge, freeze switch, high pressure switches.
4.Unit shall include a minimum of one
5.Shall include integrated defrost system to prevent excessive frost accumulation during heating duty, and shall be controlled as follows:
a.Defrost shall be initiated on the basis of time and coil temperature.
b.A 30,60,90,120 minute timer shall activate the defrost cycle only if the coil temperature is low enough to indic- ate a heavy frost condition.
c.Defrost cycle shall terminate when defrost thermostat are satisfied and shall have a positive termination time of 10 minutes.
6.Defrost system shall also include:
a.Defrost Cycle Indicator LED.
b.Dip switch selectable defrost time between 30,60,90 and 120 minutes. Factory set at 30 minutes.
c.Molded plug connection to insure proper connection.
23 09 33.23.B. Safeties:
1.Compressor
2.Loss of charge switch.
a.Units with 2 compressors shall have different sized connectors for the circuit 1 and circuit 2 low and high pres- sure switches. They shall physically prevent the
b.Loss of charge switch shall use different color wire than the high pressure switch. The purpose is to assist the installer and service technician to correctly wire and or troubleshoot the rooftop unit.
3.
a.Units with 2 compressors shall have different sized connectors for the circuit 1 and circuit 2 low and high pres- sure switches. They shall physically prevent the
b.High pressure switch shall use different color wire than the low pressure switch. The purpose is to assist the installer and service technician to correctly wire and or troubleshoot the rooftop unit.
4.Freeze protection thermostat, evaporator coil.
5.Automatic reset, motor thermal overload protector.
23 09 93 Sequence of Operations for HVAC Controls
23 09 93.13 Decentralized, Rooftop Units:
23 09 93.13 INSERT SEQUENCE OF OPERATION
548J
69