At the end of the defrost cycle, the electric heaters (if installed) will be deenergized; the reversing valves switch and the
If the space thermostat is satisfied during a defrost cycle, the unit will continue in the Defrost mode until the time or temperature constraints are satisfied.
Automatic changeover
When the system selection switch is set at AUTO. position, unit automatically changes from heating operation to cooling operation when the temperature of the conditioned space rises to the cooling level setting. When the temperature of the conditioned space falls to the heating level setting, unit automatically changes from cooling to heating operation (with a 3°F deadband in between).
Continuous air circulation
Turn unit power on. Set system control at OFF position. Set fan switch at ON position. The
Cycle-LOC™ protection
If unit operation is interrupted by an open
NOTE: If the unit fails to operate due to compressor
Emergency heat
If compressor is inoperative due to a tripped safety device (high or low pressure, indoor coil freeze stat, overcurrent, or overtemperature), the