Bryant 569C installation instructions Ð Electrical Data

Models: 569C

1 20
Download 20 pages 233 b
Page 8
Image 8
Table 4 Ð Electrical Data

Table 4 Ð Electrical Data

UNIT

NOMINAL VOLTAGE

VOLTAGE RANGE

COMPRESSOR

OFM

POWER SUPPLY

(V-Ph-Hz)

Min

Max

RLA

LRA

FLA

MCA

MOCP

 

 

208/230-3-60

187

254

21.8

142

1.9

25.6

35

569C072

460-3-60

414

508

9.6

72

1.0

12.9

15

575-3-60

518

632

7.6

58

1.9

11.4

15

 

220-3-50

198

242

19.0

142

1.0

25.6

35

 

400-3-50

360

440

9.5

72

1.0

12.9

15

 

208/230-3-60

187

254

28.8

195

3.8

39.8

45

569C090

460-3-60

414

508

14.7

95

1.9

20.3

20

575-3-60

518

632

10.8

80

1.9

15.4

15

 

220-3-50

198

242

28.8

195

1.5

37.5

45

 

400-3-50

360

440

14.7

90

1.5

19.9

20

 

208/230-3-60

187

254

37.8

239

3.1

46.2

60

569C120

460-3-60

414

508

17.2

125

1.4

22.7

30

575-3-60

518

632

12.3

80

1.4

19.3

25

 

220-3-50

198

242

37.8

239

1.4

46.2

60

 

400-3-50

360

440

17.2

114

1.4

22.7

30

 

208/230-3-60

187

254

31.5

160

3.1

42.5

50

 

380-3-60

342

418

19.0

75

2.2

26.0

35

576B090

460-3-60

414

508

15.7

80

1.4

21.0

25

575-3-60

518

632

12.6

64

1.4

17.2

20

 

 

220-3-50

198

253

31.5

160

1.4

42.5

50

 

400-3-50

342

460

15.7

80

1.4

21.0

25

 

208/230-3-60

187

254

39.7

198

3.1

52.7

70

 

380-3-60

342

418

24.0

93

2.2

32.2

40

576B102

460-3-60

414

508

19.9

99

1.4

26.3

35

575-3-60

518

632

15.9

79

1.4

21.3

25

 

 

220-3-50

198

253

39.7

198

1.4

52.7

70

 

400-3-50

342

460

19.9

99

1.4

26.3

35

 

208/230-3-60

187

254

39.7

198

3.1

52.7

70

 

380-3-60

342

418

24.0

93

2.2

32.2

40

576B120

460-3-60

414

508

19.9

99

1.4

26.3

35

575-3-60

518

632

15.9

79

1.4

21.3

25

 

 

220-3-50

198

253

39.7

198

1.4

52.7

70

 

400-3-50

342

460

19.9

99

1.4

26.3

35

LEGEND

Example: Supply voltage is 460-3-60.

CSA

Ð Canadian Standards Association

FLA

Ð Full Load Amps

HACR

Ð Heating, Air Conditioning and Refrigeration

LRA

Ð Locked Rotor Amps

MCA

Ð Minimum Circuit Amps

MOCP Ð Maximum Overcurrent Protection

AB = 452 v

BC = 464 v

AC = 455 v

Average Voltage =

452 + 464 + 455

3

NEC

Ð National Electrical Code (U.S.A. Standard)

OFM

Ð Outdoor (Condenser) Fan Motor

RLA

Ð Rated Load Amps

=

1371

3

UL

Ð Underwriters' Laboratories

= 457

(AB) 457 - 452 = 5 v (BC) 464 - 457 = 7 v

(AC) 457 - 455 = 2 v Maximum deviation is 7 v. Determine percent voltage imbalance

% Voltage Imbalance = 100 x

7

NOTES:

1.In compliance with NEC requirements for multimotor and combina- tion load equipment (refer to NEC Articles 430 and 440), the over- current protective device for the unit shall be fuse or HACR breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent voltage imbalance.

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maxi- mum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

3.The 575-v units are CSA only.

4.The 380-v units are not UL or CSA listed.

= 100 x

max voltage deviation from average voltage

average voltage

Ð8Ð

Page 8
Image 8
Bryant 569C installation instructions Ð Electrical Data