2.Avoid abrupt duct size increases and reductions. Abrupt change in duct size adversely affects air performance.
IMPORTANT: Use flexible connectors between ductwork and unit to prevent transmission of vibration. Use suitable gaskets to ensure weather tight and airtight seal. When electric heat is installed, use fireproof canvas (or similar heat resistant material) connector between ductwork and unit discharge connection. If flexible duct is used, insert a sheet metal sleeve inside duct. Heat resistant duct connector (or sheet metal sleeve) must extend
3.Size ductwork for max possible air flow (See Table 1).
4.Seal, insulate, and weatherproof all external ductwork. Seal, insulate and cover with a vapor barrier all ductwork passing through conditioned spaces. Follow latest Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors Association (ACCA) minimum installation standards for residential heating and air conditioning systems.
5.Secure all ducts to building structure. Flash, weatherproof, and
6.Read unit rating plate for any required clearances around ductwork.
Configuring Units for Downflow (Vertical) Discharge
!WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system and install lockout tag. There may be more than one disconnect switch.
1.Open all electrical disconnects before starting any service work.
2.Remove horizontal (metal) duct covers to access vertical (downflow) discharge duct knockouts in unit basepan. (See Fig. 8.)
!CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Collect ALL screws that were removed. Do not leave screws on rooftop as permanent damage to the roof may occur.
To remove downflow return and supply knockout covers, break front and right side connecting tabs with a screwdriver and hammer. Push cover down to break rear and left side tabs.
NOTE: These panels are held in place with tabs similar to an electrical knockout. Reinstall horizontal duct covers (see Fig. 8) shipped on unit from factory. Insure openings are air and watertight.
The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of
Adhere to the following criteria when selecting, sizing, and installing the duct system:
1.Units are shipped for horizontal duct installation (by removing duct covers).
Horizontal Duct Covers
A09076
Basepan |
| |
Downflow |
| |
(Vertical) | Basepan | |
Supply | ||
Downflow | ||
Knockout | ||
(Vertical) | ||
| ||
| Return | |
| Knockout | |
| A09077 |
Fig. 8 - Supply and Return Duct Opening
2.Select and size ductwork,
3.Use flexible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be screwed or bolted to duct flanges. Use suitable gaskets to ensure
4.All units must have
5.Size all ductwork for maximum required airflow (either heating or cooling) for unit being installed. Avoid abrupt duct size increases or decreases or performance may be affected.
6.Adequately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through unconditioned space, and use vapor barrier in accordance with latest issue of Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors of America (ACCA) minimum installation standards for heating and air conditioning systems. Secure all ducts to building structure.
7.Flash, weatherproof, and vibration isolate all openings in building structure in accordance with local codes and good building practices.
Provide for Condensate Disposal
NOTE: Ensure that
The units dispose of condensate through a 3/4
10