Bryant 577D----A installation instructions PhysicalData Con’t - Unit 577D--A, 577D-- --A

Models: 577D----A

1 40
Download 40 pages 54.65 Kb
Page 8
Image 8
Table 1—Physical Data (Con’t) - Unit 577D--A

577D-- -- A

Table 1—Physical Data (Con’t) - Unit 577D--A

UNIT SIZE

48090

 

 

48115

 

48130

 

 

60090

 

60115

 

60130

NOMINAL COOLING CAPACITY (ton)

4

 

 

4

 

4

 

 

5

 

5

 

5

NOMINAL HEATING CAPACITY (Btu)

90,000

 

 

115,000

 

130,000

 

 

90,000

 

115,000

 

130,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHIPPING WEIGHT (lb)

558

 

 

558

 

558

 

 

609

 

609

 

609

(kg)

253

 

 

253

 

253

 

 

276

 

276

 

276

 

 

 

 

 

 

 

 

 

 

 

 

 

COMPRESSORS

 

 

 

 

 

2--- Stage

 

Scroll

 

 

 

 

Quantity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REFRIGERANT: PURON (R---410A)

15.3

 

 

15.3

 

15.3

 

 

15.8

 

15.8

 

15.8

Quantity (lb)

 

 

 

 

 

 

 

(kg)

6.9

 

 

6.9

 

6.9

 

 

7.2

 

7.2

 

7.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REFRIGERANT METERING DEVICE

 

 

 

 

 

 

TXV

 

 

 

 

Size

 

 

 

 

 

 

 

 

 

 

 

 

4 Ton

 

 

4 Ton

 

4 Ton

 

 

5 Ton

 

5 Ton

 

5 Ton

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Cfm

3300

 

 

3300

 

3300

 

 

3300

 

3300

 

3300

Diameter (in.)

22

 

 

22

 

22

 

 

22

 

22

 

22

(mm)

559

 

 

559

 

559

 

 

559

 

559

 

559

Motor Hp (Rpm)

1/4 (1100)

 

 

1/4 (1100)

 

1/4 (1100)

 

 

1/3 (1110)

 

1/3 (1110)

 

1/3 (1110)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

Rows...Fins/in.

2...21

 

 

2...21

 

2...21

 

 

2...21

 

2...21

 

2...21

Face Area (sq ft)

19.4

 

 

19.4

 

19.4

 

 

23.3

 

23.3

 

23.3

INDOOR COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

Rows...Fins/in.

3...17

 

 

3...17

 

3...17

 

 

4...17

 

4...17

 

4...17

Face Area (sq ft)

5.7

 

 

5.7

 

5.7

 

 

5.7

 

5.7

 

5.7

INDOOR FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Airflow (Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

Comfort

 

Variable based on Comfort Roll back (see User Interface instructions for more information).

 

Efficiency

1400

 

 

1400

 

1400

 

 

1750

 

1750

 

1750

 

 

 

 

 

Max

1600

 

 

1600

 

1600

 

 

2000

 

2000

 

2000

Furnace (gas ht.) airflow--- Low Stage

815

 

 

1215

 

1255

 

 

845

 

1215

 

1255

Furnace (gas ht.) airflow--- High Stage

1385

 

 

1885

 

1875

 

 

1300

 

1910

 

1920

Size (in.)

11x10

 

 

11x10

 

11x10

 

 

11x10

 

11x10

 

11x10

(mm)

279x254

 

 

279x254

 

279x254

 

 

279x254

 

279x254

 

279x254

Motor HP (RPM)

3/4

 

 

3/4

 

3/4

 

 

1

 

1

 

1

FURNACE SECTION*

 

 

 

 

 

 

 

 

 

 

 

 

 

Burner Orifice No. (Qty...Drill Size)

 

 

 

 

 

 

 

 

 

 

 

 

 

Natural Gas (Factory Installed)

3...38

 

 

3...33

 

3...31

 

 

3...38

 

3...33

 

3...31

Propane Gas

3...53

 

 

3...51

 

3...49

 

 

3...53

 

3...51

 

3...49

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH---PRESSURE SWITCH (psig)

 

 

 

 

 

 

670 ± 10

 

 

 

 

Cut--- out

 

 

 

 

 

 

 

 

 

 

Reset (Auto)

 

 

 

 

 

 

470 ± 25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH---PRESSURE SWITCH 2 (psig)

 

 

 

 

 

 

 

 

 

 

 

 

 

(Compressor Solenoid)

 

 

 

 

 

 

565 ± 15

 

 

 

 

Cut--- out

 

 

 

 

 

 

 

 

 

 

Reset (Auto)

 

 

 

 

 

 

455 ± 15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOSS---OF---CHARGE /

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW---PRESSURE SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

(Liquid Line) (psig)

 

 

 

 

 

 

23 ± 5

 

 

 

 

Cut--- out

 

 

 

 

 

 

 

 

 

 

Reset (auto)

 

 

 

 

 

 

55 ± 5

 

 

 

 

RETURN---AIR FILTERS Throwaway† (in.)

 

 

 

 

 

 

24x36x1

 

 

 

 

(mm)

 

 

 

 

 

610x914x25

 

 

 

 

*Based on altitude of 0 to 2000 ft (0 to 610 m).

 

 

 

 

 

 

 

 

 

 

 

 

 

{Recommended filter sizes for field---installed air filter grilles mounted on the wall or ceiling of the conditioned structure. Required filter sizes shown are based on the larger of the AHRI (Air Conditioning, Heating and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute for throwaway type or 450 ft/minute for high ---capacity type. Air filter pressure drop for non ---standard filters must not exceed 0.08 IN. W.C.

8

Page 8
Image 8