Section 3 - Operation

Bryant Liquid-cooled 25 kW Generator

‹ 3.1.3 15 AMP FUSE

 

‹ 3.1.6 SYSTEM READY LED

This fuse protects the control console’s DC control circuit against electrical overload and is located inside the control panel. If the fuse has melted open because of an overload, engine cranking and startup cannot occur. If the fuse needs to be replaced, use only an identical 15-amp replacement fuse (type ATO).

‹3.1.4 5 AMP FUSE

This fuse protects the battery charger against electri- cal overload and is located inside the control panel. If the fuse needs to be replaced, use only an identical 5- amp replacement fuse (type ATO).

NOTE:

This fuse will not remove the + battery input power from the PCB when it opens. This means the exercise timer will not be reset.

The System Ready LED (green) has two main pro- poses. First, the LED will be ON when the AUTO/OFF/MANUAL switch is in the AUTO position, utility is present, and there are no system alarms. This ON state indicates the system is fully ready for automatic operation.

The system ready LED will be OFF when the switch is in the manual or OFF positions.

The system ready LED is also used to indicate the presence of utility sensing at the PCB when the switch is either in the AUTO or MANUAL modes. The LED will flash at the rate of 1/2 second on, 1/2 second off if the utility sensing level is below the transfer back threshold.

This secondary function is only available with dip switch two in the OFF position (ATS - automatic transfer switch application).

‹3.1.5 SET EXERCISE TIME SWITCH

This switch allows programming the generator to start and exercise automatically. “See Weekly Exercise Cycle.”

 

Condition

System

Low

Low

High

Over

 

Over

Switch Position

 

 

 

Ready (Green)

Bat (Red)

Oil (Red)

Temp (Red)

Speed (Red)

 

Crank (Red)

Manual

Auto

Off

 

 

Generator Switch is

OFF

X

OFF

OFF

OFF

 

OFF

 

 

O

 

 

in the OFF Mode.

 

 

 

 

 

 

 

 

 

 

 

 

System Ready for

ON

X

OFF

OFF

OFF

 

OFF

 

O

 

 

 

Automatic Start

 

 

 

 

 

 

 

 

 

 

 

 

Generator Switch is

OFF

X

OFF

OFF

OFF

 

OFF

O

 

 

 

 

in the MANUAL Mode

 

 

 

 

 

 

 

 

 

 

 

 

Weekly Exerciser

X

Flashing

Flashing

Flashing

Flashing

 

Flashing

O

O

O

 

 

is not set

 

(-----------------------------------

1 sec rate

---------------------------------------

)

 

 

 

 

 

Battery Voltage <12V

X

ON

 

 

 

 

 

O

O

O

 

 

for >1 minute

 

(Non-latching)

 

 

 

 

 

 

 

 

 

 

Battery Voltage <6V

X

ON

 

 

 

 

 

O

O

 

 

 

Unit Shutdown due

OFF

X

ON

 

 

 

 

O

O

 

 

 

to Low Oil Pressure

 

 

 

 

 

 

 

 

 

 

 

 

Unit Shutdown due

OFF

X

 

ON

 

 

 

O

O

 

 

 

to High Temperature

 

 

 

 

 

 

 

 

 

 

 

 

Unit Shutdown due

OFF

X

 

 

ON

 

 

O

O

 

 

 

to Engine Overspeed

 

 

 

 

 

 

 

 

 

 

 

 

Unit Failed to Start

OFF

X

 

 

 

 

ON

O

O

 

 

 

during it’s Crank Cycle

 

 

 

 

 

 

 

 

 

 

 

 

Utility Voltage is

Flashing

X

 

 

 

 

 

O

O

 

 

 

<45% of Nominal

1 sec rate

 

 

 

 

 

 

 

 

 

 

 

Engine Speed Signal Fault

OFF

X

 

 

Flashing

 

 

O

O

 

 

 

Control Board Dip Switch

OFF

X

The five RED LED’s will turn on one at a time

 

O

O

O

 

 

is in wrong position.

 

 

 

 

 

 

 

 

 

 

 

 

 

X = indicates that the LED can be ON or OFF depending on the operating conditions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 