Bunn H10X SERVICE cont Electronic Controls cont, Temperature Control Flow Charts cont

Models: H10X

1 20
Download 20 pages 20.7 Kb
Page 12
Image 12
Temperature Control Flow Charts (cont.)

SERVICE (cont.)

Electronic Controls (cont.)

Temperature Control Flow Charts (cont.)

H10X THERMOSTAT

PROBLEM: Boils Excessively - Fills Cup

If the indicator was on or blinking, the temperature sensor is operating properly, proceed to #7.

If the indicator was off, check the sensor connection on the electronic control circuit board and/or replace the temperature sensor and the electronic control as- sembly.

NOTE - Each temperature sensor is calibrated to an electronic control assembly. Both components MUST

Drain cup

Retry

Heater Light On While

Boiling

?

No

Yes

Replace Steam Sensor

be replaced as a set.

7. Check the voltage across the tank heater terminals

with a voltmeter. Connect the dispenser to the

power source. The indication must be 200 to 240

volts ac for 200 to 240 volt models while the red

Disconnect Blue Wire From

Control Board Pin 7

Retry

Still Boiling

?

No

Finished

Yes

Replace Control Assembly

indicator on the circuit board is on or blinking.

8. Disconnect the dispenser from the power source.

Still Boiling

?

No

Yes

Replace Triac Assembly

Check For Split

Tank Heater

If voltage was present as described, the temperature control of the system is operating properly.

Replace Control Assembly

Temperature Control Test Procedure

1.Disconnect the dispenser from the power source.

2.Check the voltage across terminals 3 & 4 of the electronic control circuit board with a voltmeter. Connect the dispenser to the power source. The indication must be 200 to 240 volts ac for 200 to 240 volt models.

3.Disconnect the dispenser from the power source.

If voltage was present as described, proceed to #4.

If voltage was not present as described, refer to the Wiring Diagram and check the dispenser wiring har- ness.

4.Connect the dispenser to the power source .

5.Observe the red indicator on the electronic control circuit board.

6.Disconnect the dispenser from the power source.

If voltage was not present as described, contact Bunn- O-Matic to order an electronic control assembly tem- perature sensor, and triac assembly for evaluation and proceed to #9.

9.Replace the electronic control assembly and tem- perature sensor.

NOTE - Each electronic control assembly is calibrated to a temperature sensor. Both components MUST be replaced as a set.

10.Check the voltage across the tank heater terminals with a voltmeter. Connect the dispenser to the power source. The indication must be 200 to 240 volts ac for 200 to 240 volt models while the red indicator on the circuit board is on or blinking.

12

10889 091599

 

Page 12
Image 12
Bunn H10X service manual SERVICE cont Electronic Controls cont, Temperature Control Flow Charts cont