Oil Cooler Ð The oil for the external gear and the com- pressor must be cooled while the compressor is running. The compressor oil cooler is a water-cooled, helical, tube-in- shell type heat exchanger. A plug valve is manually set to maintain proper temperatures. Set the valve to maintain a 145 F (63 C) oil sump temperature while the compressor is running.

The gear oil cooler is a water-cooled, helical tube-in-shell type heat exchanger. A plug valve is manually set to main- tain proper temperatures. Set the valve to maintain the oil temperature leaving the cooler at 130 F (54 C) while the com- pressor is running.

Remote Start/Stop Controls Ð A remote device, such as a time clock with a set of contacts, may be used to start and stop the chiller. However, the device should not be pro- grammed to start and stop the chiller more than 2 or 3 times every 12 hours. If more than 8 starts in 12 hours occur, the Excessive Starts alarm is displayed, and the chiller is pre- vented from starting. The operator must reset the alarm at the LID in order to override the starts counter and start the chiller. If the automatic restart after a power failure (AUTO RESTART OPTION ) is not activated (disabled) when a power failure occurs and the remote contact is closed, the PIC con- trol activates an alarm because of the loss of voltage.

The contacts for remote starting are wired into the starter at terminal strip TB5, terminals 8A and 8B. See the certi®ed drawings for further details on contact ratings. The contacts must be dry (no power).

Spare Safety Inputs Ð Normally closed (NC) digital inputs for additional ®eld-supplied safeties may be wired to the spare protective limits input channel in place of the factory- installed jumper. (Wire multiple inputs in series.) Opening any contact results in a safety shutdown and LID display. Refer to the certi®ed drawings for safety contact ratings.

Analog temperature sensors may also be added to the op- tions modules, if installed. These may be programmed to ac- tivate an alert on the CCN network, but not shut down the chiller.

Spare Alarm Contacts Ð Two spare sets of alarm con- tacts are provided in the starter. The contact ratings are pro- vided in the certi®ed drawings. The contacts are located on terminal strip TB6, terminals 5A and 5B, and terminals 5C and 5D.

Condenser Pump Control Ð The chiller monitors the condenser pressure (CONDENSER PRESSURE param- eter on the STATUS01 screen) and may turn on the con- denser pump if the pressure becomes too high whenever the compressor is shut down. The condenser pressure override (COND PRESSURE OVERRIDE parameter on the SERVICE1 screen) is the value that determines this pressure point. Its default value is 125 psi (862 kPa). If the condenser pressure is greater than or equal to the condenser pressure override, and the entering condenser water temperature (EN- TERING CONDENSER WATER parameter on the STATUS01 screen) is less than 115 F (46 C), then the con- denser pump energizes to try to decrease the pressure. The pump turns off when the condenser pressure is 5psi (34 kPa) less than the pressure override, or when the condenser re- frigerant temperature (CONDENSER REFRIG TEMP on the STATUS01 screen) is within 3° F (2° C) of the entering con- denser water temperature.

Condenser Freeze Prevention Ð This control al- gorithm helps prevent condenser tube freeze-up by energiz- ing the condenser pump relay. If the pump is controlled by the PIC, starting the pump helps prevent the water in the condenser from freezing. Condenser freeze prevention can occur whenever the chiller is not running except when it is either actively in pumpdown or in pumpdown lockout with the freeze prevention disabled.

When the condenser refrigerant temperature is less than or equal to the condenser freeze point (CONDENSER FREEZE POINT on the SERVICE1 screen), or the entering condenser water temperature is less than or equal to the condenser freeze point, then the condenser water pump (CONDENSER WA- TER PUMP on the STATUS02 screen) is energized until the condenser refrigerant temperature is greater than the con- denser freeze point plus 5° F (2.7° C). If the chiller is in PUMPDOWN mode and the pump is energized, the PIC ac- tivates an alarm. If the chiller is not in PUMPDOWN mode and the pump is energized, the PIC activates an alert. If the chiller is in RECYCLE shutdown mode, the mode transi- tions to SHUTDOWN (non-recycle shutdown).

Tower-Fan Relay Ð This control can be used to assist the condenser water temperature control system (®eld sup- plied). Low condenser water temperature can cause the chiller to shut down on low refrigerant temperature. The tower fan relay, located in the starter, is controlled by the PIC to en- ergize and deenergize as the pressure differential between cooler and condenser vessels changes. This function pre- vents low condenser water temperature and maximizes chiller efficiency. The tower-fan relay can only accomplish this if the relay has been added to the cooling tower temperature controller. The tower-fan relay (TOWER FAN RELAY on the STATUS02 screen) is turned on whenever the condenser wa- ter pump is running, ¯ow is veri®ed, and the difference be- tween cooler and condenser pressure is more than 30 psid (207 kPad) or entering condenser water temperature is greater than 85 F (29 C). The tower-fan relay is deenergized when- ever the condenser pump is off, ¯ow is lost, the evaporator refrigerant temperature is less than the override temperature, or the differential pressure is less than 28 psid (193 kPad) and entering condensing water is less than 80 F (27 C).

IMPORTANT: A ®eld-supplied water temperature con- trol system for condenser water should be installed. The system should maintain the leaving condenser wa- ter temperature at 20° F (11° C) above the leaving chilled water temperature.

The tower-fan relay control is not a substitute for a con- denser water temperature control. When used with a wa- ter temperature control system, the tower-fan relay con- trol can be used to help prevent low condenser water temperatures and associated problems.

Auto. Restart After Power Failure Ð This option, which may be viewed or modi®ed on the CONFIG screen (the AUTO RESTART OPTION parameter), can be enabled or disabled. If this option is enabled, the chiller starts up au- tomatically after a single cycle dropout; low, high, or no volt- age; and the power is within ±10% of normal. The 15-minutestart-to-start timer and the stop-to-start timer are ignored during this type of start-up.

When power is restored after a power failure, and if the compressor had been running, the oil pump is energized for one minute before the evaporator pump is energized. The Auto. Restart function then continues like a normal start-up.

36

Page 36
Image 36
Carrier 17EX specifications

17EX specifications

The Carrier 17EX is recognized as an innovative air conditioning solution that combines efficiency with advanced technology. This model is designed to meet the increasing demands of residential and commercial cooling needs while maintaining environmental consciousness.

One of the standout features of the Carrier 17EX is its impressive Seasonal Energy Efficiency Ratio (SEER) rating. With a SEER rating that often exceeds 17, this unit ensures optimized energy consumption, significantly lowering operational costs for users. The incorporation of advanced compressor technology allows the system to adjust its cooling output based on the specific needs of the environment, thus providing both comfort and energy savings.

The Carrier 17EX utilizes a variable-speed inverter-driven compressor that enhances its performance and adaptability. This technology allows the air conditioning unit to operate at different speeds, intelligently adjusting to changing load conditions. As a result, the system runs more efficiently and quietly, providing a more consistent comfort level without the abrupt temperature swings associated with traditional units.

In addition to efficiency, the Carrier 17EX also prioritizes reliability and durability. The unit comes with a robust cabinet that protects the components from weather elements, ensuring longevity and consistent performance. The innovative design integrates a corrosion-resistant finish and robust insulation, which further enhances the unit's resilience in various environmental conditions.

For users concerned about indoor air quality, the Carrier 17EX includes advanced filtration systems designed to capture allergens and airborne particles. This feature is particularly beneficial for individuals with respiratory issues, ensuring that the air circulated within the space is clean and healthy.

Moreover, the Carrier 17EX is equipped with smart technology capabilities, allowing users to control their systems remotely through smartphones or other smart devices. This connectivity not only provides convenience but also empowers homeowners to optimize their energy use by adjusting settings on the fly, ensuring efficient operation even when they are away from home.

Overall, the Carrier 17EX stands out in the marketplace for its exceptional energy efficiency, advanced technology, and commitment to providing reliable and effective cooling solutions. Its combination of modern features makes it a preferred choice for those looking to enhance comfort while being mindful of energy consumption and environmental impact.