Table 2 — LID Display Data (cont)
EXAMPLE 7 — LEAD/LAG CONFIGURATION DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU .
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT .
5. Scroll down to highlight LEAD/LAG.
6. Press SELECT .LEAD/LAG CONFIGURATION SCREEN
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
LEAD/LAG SELECT
DISABLE =0, LEAD =1,
LAG =2, STANDBY =3 0-3 leadlag 0
Load Balance Option DISABLE/ENABLE loadbal DISABLE
Common Sensor Option DISABLE/ENABLE commsens DISABLE
LAG Percent Capacity 25-75 % lag per 50
LAG Address 1-236 lag add 92
LAG START Timer 2-60 MIN lagstart 10
LAG STOP Timer 2-60 MIN lagstop 10
PRESTART FAULT Timer 0-30 MIN preflt 5
STANDBY Chiller Option DISABLE/ENABLE stndopt DISABLE
STANDBY Percent Capacity 25-75 % stnd per 50
STANDBY Address 1-236 stnd add 93
27