4.A high pressure point can also be calibrated between 240 and 260 psig (1655 and 1793 kPa) by attaching a regu- lated 250 psig (1724 kPa) pressure (usually from a ni- trogen cylinder). The high pressure point can be calibrated by accessing the appropriate transducer on the

STATUS01 screen, highlighting the transducer, pressing

the SELECT softkey, and then increasing or decreasing the value to the exact pressure on the refrigerant gage.

Press ENTER to ®nish. High altitude locations must com- pensate the pressure so that the temperature/pressure re- lationship is correct.

If the transducer reading returns to the previous value and the pressure is within the allowed range, check the volt- age ratio of the transducer. Refer to Step 3 above. The voltage ratio for this high pressure calibration must be between 0.585 and 0.634 vdc to allow calibration. Change the pressure at the transducer until the ratio is within the acceptable range. Then attempt to calibrate to the new pressure input.

The PIC will not allow calibration if the transducer is too far out of calibration. A new transducer must be installed and re-calibrated.

OIL DIFFERENTIAL PRESSURE/POWER SUPPLY MOD- ULE CALIBRATION Ð (See Fig. 48.) The oil reservoir in the 17EX chiller is not common to cooler pressure. There- fore, a comparison of pump output to cooler pressure can not be used to provide differential oil pressure information. A different method has been developed.

Oil transmission sump pressure and oil supply pressure are fed to a comparator circuit on a 5V power supply board. The output of this circuit, which represents differential oil pressure, is fed to the PSIO. The oil differential pressure is calibrated to 0 psid (0 kPad) by selecting the oil pressure input on the STATUS01 screen. Then, with the oil pump turned

OFF and the transducers connected, press the ENTER soft-

key to zero the point. No high end calibration is needed or possible.

17EX OIL PRESSURE INPUT

Fig. 48 Ð Oil Differential Pressure/Power

Supply Module

TROUBLESHOOTING TRANSDUCERS Ð When trouble- shooting transducers, keep the negative lead of your volt- ohmmeter on terminal U4 of the power supply (or terminal 4 on power supplies without the comparator circuit).

Voltage VO1 = (VH1-VL1) + .467 ± .1 V

For all PIC transducers:

Measured pressure = (507.97 × (V out/Vin) ) − 47.33

Vout = transducer output ref. to neg. terminal (4 or U4) i.e., VH1 to U4 or VL1 to U4

Vin = power supply output, i.e., U3 to U4

TRANSDUCER REPLACEMENT Ð Since the transduc- ers are mounted on Schrader-type ®ttings, there is no need to remove refrigerant from the vessel. Disconnect the trans- ducer wiring by pulling up on the locking tab while pulling up on the weather-tight connecting plug from the end of the transducer. Do not pull on the transducer wires. Unscrew the transducer from the Schrader ®tting. When installing a new transducer, do not use pipe sealer, which can plug the sensor. Put the plug connector back on the sensor and snap into place. Check for refrigerant leaks.

Make sure to use a backup wrench on the Schrader ®t- ting whenever removing a transducer.

Control Algorithms Checkout Procedure Ð One of the tables in the SERVICE menu is the CONTROL AL- GORITHM STATUS table. This table has 6 screens that may be viewed to see how a particular control algorithm is operating, that is, to see what parameters and values the PIC is using to control the chiller.

MAINT01

Capacity

The values used to calculate the chilled

 

Control

water/brine control point.

MAINT02

Override

Details of all chilled water control over-

 

Status

ride values

MAINT03

Surge/

The surge and hot gas bypass control

 

HGBP

algorithm status as well as the values

 

Status

dealing with this control.

MAINT04

LEAD/LAG

LEAD/LAG operation status.

 

Status

 

OCCDEFM

Time

The Local and CCN occupied sched-

 

Schedules

ules, displayed in a way that allows the

 

Status

operator to quickly determine whether

 

 

the schedule is in an occupied period

 

 

or not.

WSMDEFME

Water

The status of the WSM (water system

 

System

manager), a CCN module that can turn

 

Manager

on the chiller and change the chilled

 

Status

water control point.

These maintenance tables are very useful in determining guide vane position, reaction from load changes, control point overrides, hot gas bypass reaction, surge prevention, etc.

Control Test Ð The control test feature can check all the thermistor temperature sensors, including those on the Options modules, pressure transducers, pumps and their as- sociated ¯ow switches, the guide vane actuator, and other control outputs, such as hot gas bypass. The tests can help to determine whether a switch is defective, or a pump relay is not operating, among other useful troubleshooting tests.

During pumpdown operations, the pumps are energized to prevent freeze-up, and the vessel pressures and tempera- tures are displayed. The pumpdown/lockout feature pre- vents the compressor from starting up when there is no re- frigerant in the chiller or when the vessels are isolated. The operator then uses the terminate lockout screen to end the pumpdown lockout after the pumpdown procedure is re- versed and refrigerant is added.

85

Page 85
Image 85
Carrier 17EX specifications MAINT01, MAINT02, MAINT03, MAINT04, Occdefm, Wsmdefme

17EX specifications

The Carrier 17EX is recognized as an innovative air conditioning solution that combines efficiency with advanced technology. This model is designed to meet the increasing demands of residential and commercial cooling needs while maintaining environmental consciousness.

One of the standout features of the Carrier 17EX is its impressive Seasonal Energy Efficiency Ratio (SEER) rating. With a SEER rating that often exceeds 17, this unit ensures optimized energy consumption, significantly lowering operational costs for users. The incorporation of advanced compressor technology allows the system to adjust its cooling output based on the specific needs of the environment, thus providing both comfort and energy savings.

The Carrier 17EX utilizes a variable-speed inverter-driven compressor that enhances its performance and adaptability. This technology allows the air conditioning unit to operate at different speeds, intelligently adjusting to changing load conditions. As a result, the system runs more efficiently and quietly, providing a more consistent comfort level without the abrupt temperature swings associated with traditional units.

In addition to efficiency, the Carrier 17EX also prioritizes reliability and durability. The unit comes with a robust cabinet that protects the components from weather elements, ensuring longevity and consistent performance. The innovative design integrates a corrosion-resistant finish and robust insulation, which further enhances the unit's resilience in various environmental conditions.

For users concerned about indoor air quality, the Carrier 17EX includes advanced filtration systems designed to capture allergens and airborne particles. This feature is particularly beneficial for individuals with respiratory issues, ensuring that the air circulated within the space is clean and healthy.

Moreover, the Carrier 17EX is equipped with smart technology capabilities, allowing users to control their systems remotely through smartphones or other smart devices. This connectivity not only provides convenience but also empowers homeowners to optimize their energy use by adjusting settings on the fly, ensuring efficient operation even when they are away from home.

Overall, the Carrier 17EX stands out in the marketplace for its exceptional energy efficiency, advanced technology, and commitment to providing reliable and effective cooling solutions. Its combination of modern features makes it a preferred choice for those looking to enhance comfort while being mindful of energy consumption and environmental impact.