Carrier 38AKS028-044 dimensions A Ð Refrigerant Piping Sizes Ð 60 Hz, Single Suction Risers

Models: 38AKS028-044

1 24
Download 24 pages 46.27 Kb
Page 5
Image 5
Table 2A Ð Refrigerant Piping Sizes Ð 60 Hz

Table 2A Ð Refrigerant Piping Sizes Ð 60 Hz

SINGLE SUCTION RISERS

UNIT

 

 

 

LENGTH OF INTERCONNECTING PIPING, FT (M)

 

 

 

16-25 (4.9-7.6)

26-50 (7.9-15.2)

51-75 (15.5-22.8)

76-100 (23.2-30.5)

101-200 (30.8-60.9)

38AKS

 

L

S

L

S

L

S

L

 

S

L

S

028

7¤8

15¤8

7¤8

21¤8*

7¤8

21¤8*

7¤8

 

21¤8*

7¤8

21¤8*

034

7¤8

21¤8

7¤8

21¤8

7¤8

21¤8

11¤8

 

21¤8

11¤8

25¤8*

044

7¤8

21¤8

7¤8

21¤8

11¤8

25¤8*

11¤8

 

25¤8*

11¤8

25¤8*

LÐ Liquid Line S Ð Suction Line

*IMPORTANT Ð Requires a double suction riser, if evaporator is below condensing unit. See table below. NOTE: Liquid and suction line sizes are OD (in.) Equivalent sizes in mm are listed below.

DOUBLE SUCTION RISERS Ð 60 Hz

UNIT

 

 

 

 

 

LENGTH OF INTERCONNECTING PIPING, FT (M)

 

 

 

 

26-50 (7.9-15.2)

 

51-75 (15.5-22.8)

 

76-100 (23.2.-30.5)

 

101-200 (30.8-60.9)

38AKS

 

 

 

 

 

A

 

B

C

A

 

 

B

 

C

A

B

 

C

A

B

C

028

13¤8

 

15¤8

21¤8

13¤8

 

 

15¤8

 

21¤8

13¤8

15¤8

 

21¤8

13¤8

15¤8

21¤8

034

Ð

 

Ð

Ð

Ð

 

Ð

Ð

Ð

Ð

Ð

 

1

5¤8

21¤8

25¤8

044

Ð

 

Ð

Ð

1 5¤8

 

 

21¤8

 

25¤8

15¤8

21¤8

 

25¤8

15¤8

21¤8

25¤8

NOTE: A, B, C dimensions relate to reference diagram.

Table 2B Ð Refrigerant Piping Sizes Ð 50 Hz

SINGLE SUCTION RISERS

UNIT

 

 

 

LENGTH OF INTERCONNECTING PIPING, FT (M)

 

 

 

16-25 (4.9-7.6)

26-50 (7.9-15.2)

51-75 (15.5-22.8)

76-100 (23.2-30.5)

101-200 (30.8-60.9)

38AKS

 

L

S

L

S

L

S

L

 

S

L

S

028

7¤8

15¤8

7¤8

21¤8*

7¤8

21¤8*

7¤8

 

21¤8*

7¤8

21¤8*

034

7¤8

21¤8²

7¤8

21¤8*

7¤8

21¤8*

11¤8

 

25¤8*

11¤8

25¤8*

044

7¤8

21¤8

7¤8

21¤8

11¤8

25¤8*

11¤8

 

25¤8*

11¤8

25¤8*

LÐ Liquid Line S Ð Suction Line

*IMPORTANT Ð Requires a double suction riser, if evaporator is below condensing unit. See table below. ²For riser, use 1 5¤8 OD inches.

NOTE: Liquid and suction line sizes are OD (in.) Equivalent sizes in mm are listed below.

DOUBLE SUCTION RISERS Ð 50 Hz

UNIT

 

 

 

 

 

LENGTH OF INTERCONNECTING PIPING, FT (M)

 

 

 

 

26-50 (7.9-15.2)

 

51-75 (15.5-22.8)

 

76-100 (23.2.-30.5)

 

101-200 (30.8-60.9)

38AKS

 

 

 

 

 

A

 

B

C

A

 

B

 

C

A

B

 

C

A

B

C

028

13¤8

 

15¤8

21¤8

13¤8

 

15¤8

 

21¤8

13¤8

15¤8

 

21¤8

13¤8

15¤8

21¤8

034

15¤8

 

15¤8

21¤8

15¤8

 

15¤8

 

21¤8

15¤8

15¤8

 

21¤8

15¤8

21¤8

25¤8

044

Ð

 

Ð

Ð

1 5¤8

 

21¤8

 

25¤8

15¤8

21¤8

 

25¤8

15¤8

21¤8

25¤8

NOTE: A, B, C dimensions relate to reference diagram.

MAXIMUM LIQUID LIFT

UNIT 38AKS

 

60 Hz

 

50 Hz

Ft

 

M

Ft

 

M

 

 

 

028

76

 

23

66

 

20

034

67

 

20

60

 

18

044

76

 

23

66

 

20

EQUIVALENT SIZES IN MM

in.

mm

7¤8

22.2

11¤8

28.6

13¤8

34.9

15¤8

41.3

21¤8

54.0

25¤8

66.7

Unit Size

Dimension Ð in. (mm)

028

15¤8

(41.3)

034

21¤8

(54.0)

044

21¤8

(54.0)

5

Page 5
Image 5
Carrier 38AKS028-044 dimensions A Ð Refrigerant Piping Sizes Ð 60 Hz, Single Suction Risers, DOUBLE SUCTION RISERS Ð 60 Hz