Power Supply Ð Electrical characteristics of available power supply must agree with unit nameplate rating. Supply voltage must be within limits shown in Table 3.
IMPORTANT: Operating unit on improper supply volt- age, or with excessive phase imbalance, constitutes abuse and may affect Carrier warranty. See Unbalanced
Power Wiring Ð All power wiring must comply with applicable local and national codes. Install
GENERAL WIRING NOTES
1.A crankcase heater is wired in the control circuit so it is always operable as long as power supply disconnect is on, even if any safety device is open or unit
2.The power circuit ®eld supply disconnect should never be open except when unit is being serviced or is to be down for a prolonged period. When operation is resumed, crank- case heater should be energized for 24 hours before start- up. If unit is to be shut down for a prolonged period, it is recommended that the suction and discharge valves be
closed to prevent an excessive accumulation of refriger- ant in the compressor oil.
3.Power entry is one end only.
4.Maximum ®eld wire sizes allowed by lugs on terminal block are:
UNIT | WIRE | ||
38AKS | SIZE* | ||
| |||
028 |
| ||
034 |
| ||
350 kcmil | |||
| |||
044 |
| ||
| |||
|
| ||
LEGEND |
|
|
AWG Ð American Wire Gage kcmil Ð Thousand Circular Mils
*All other units use 2/0 AWG (67.4 mm2).
5.Terminals for ®eld power supply are suitable for copper,
CONDENSER FANS Ð The fans must rotate counterclock- wise when viewed from above. If necessary, correct direc- tion of fan rotation by interchanging any 2 power input wires at disconnect switch. Affix crankcase heater decal (located in installer's packet) to unit disconnect switch.
Table 3 Ð Electrical Data
60 HZ
| UNIT |
|
| UNIT |
|
|
|
| COMPRESSOR | FAN MOTORS | ||||
| Volts | Supplied* |
|
|
| MOCP |
|
|
|
|
| |||
38AKS |
| MCA |
| ICF | RLA | LRA | FLA (ea) | Qty | ||||||
3 Ph, 60 Hz | Min. | Max. |
|
| (Fuse) | |||||||||
|
|
|
|
|
|
|
|
|
|
| ||||
|
| 500 | 208/230 | 187 | 254 |
| 124.6 |
| 200 | 452.2 | 89.8 | 446 | 6.2 | 2 |
028 |
| 200 | 380 | 342 | 418 |
| 64.7 |
| 110 | 250.9 | 45.5 | 247 | 3.9 | 2 |
| 600 | 460 | 414 | 508 |
| 60.7 |
| 100 | 226.1 | 43.6 | 223 | 3.1 | 2 | |
|
|
|
| |||||||||||
|
| 100 | 575 | 518 | 632 |
| 52.5 |
| 80 | 167.4 | 36.5 | 164 | 3.4 | 2 |
|
| 500 | 208/230 | 187 | 254 |
| 145.5 |
| 250 | 512.2 | 106.5 | 506 | 6.2 | 2 |
034 |
| 200 | 380 | 342 | 418 |
| 72.5 |
| 125 | 283.9 | 52.6 | 280 | 3.9 | 2 |
| 600 | 460 | 414 | 508 |
| 68.7 |
| 110 | 256.1 | 50.0 | 253 | 3.1 | 2 | |
|
|
|
| |||||||||||
|
| 100 | 575 | 518 | 632 |
| 54.9 |
| 90 | 179.4 | 38.5 | 176 | 3.4 | 2 |
|
| 500 | 230 | 187 | 254 |
| 203.0 |
| 350 | 702.4 | 147.5 | 690 | 6.2 | 3 |
044 |
| 200 | 380 | 342 | 418 |
| 111.1 |
| 175 | 389.8 | 79.5 | 382 | 3.9 | 3 |
| 600 | 460 | 414 | 508 |
| 91.0 |
| 150 | 351.2 | 65.4 | 345 | 3.1 | 3 | |
|
|
|
| |||||||||||
|
| 100 | 575 | 518 | 632 |
| 81.5 |
| 125 | 282.8 | 57.1 | 276 | 3.4 | 3 |
|
|
|
|
|
|
|
| 50 HZ |
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| |||
| UNIT |
|
| UNIT |
|
|
|
| COMPRESSOR | FAN MOTORS | ||||
| Volts | Supplied* |
|
|
| MOCP |
|
|
|
|
| |||
38AKS |
| MCA |
| ICF | RLA | LRA | FLA (ea) | Qty | ||||||
3 Ph, 50 Hz | Min. | Max. |
|
| (Fuse) | |||||||||
|
|
|
|
|
|
|
|
|
|
| ||||
|
| 800 | 230 | 198 | 254 |
| 109.0 |
| 175 | 348.4 | 76.9 | 342 | 6.4 | 2 |
028 |
| 300 | 346 | 311 | 380 |
| 64.9 |
| 100 | 263.4 | 44.9 | 259 | 4.4 | 2 |
|
| 900 | 400 | 342 | 400 |
| 60.5 |
| 100 | 226.0 | 43.6 | 223 | 3.0 | 2 |
|
| 800 | 230 | 198 | 254 |
| 120.2 |
| 200 | 372.4 | 85.9 | 366 | 6.4 | 2 |
034 |
| 300 | 346 | 311 | 380 |
| 76.1 |
| 125 | 298.4 | 53.9 | 294 | 4.4 | 2 |
|
| 900 | 400 | 342 | 400 |
| 68.5 |
| 110 | 256.0 | 50.0 | 253 | 3.0 | 2 |
|
| 800 | 230 | 198 | 254 |
| 150.6 |
| 250 | 557.8 | 105.1 | 545 | 6.4 | 3 |
044 |
| 300 | 346 | 311 | 380 |
| 112.6 |
| 175 | 408.8 | 79.5 | 400 | 4.4 | 3 |
|
| 900 | 400 | 342 | 400 |
| 90.8 |
| 150 | 351.0 | 65.4 | 345 | 3.0 | 3 |
| LEGEND |
CSA | Ð Canadian Standards Association |
FLA | Ð Full Load Amps |
ICF | Ð Maximum Instantaneous Current Flow during starting (the point |
| in the starting sequence where the sum of the LRA for the start- |
| ing compressor, plus the total FLA for all running fan motors is |
| maximum). |
LRA | Ð Locked Rotor Amps |
MCA | Ð Minimum Circuit Amps (complies with National |
| Electrical Code [NEC, U.S.A.], Section |
MOCP Ð Maximum Overcurrent Protection | |
RLA | Ð Rated Load Amps |
UL | Ð Underwriters' Laboratories |
*Units are suitable for use on electrical systems where voltage sup- plied to unit terminals is not below or above listed minimum and maxi- mum limits.