Carrier 38AKS028-044 dimensions Ð Electrical Data

Models: 38AKS028-044

1 24
Download 24 pages 46.27 Kb
Page 6
Image 6
Table 3 Ð Electrical Data

Power Supply Ð Electrical characteristics of available power supply must agree with unit nameplate rating. Supply voltage must be within limits shown in Table 3.

IMPORTANT: Operating unit on improper supply volt- age, or with excessive phase imbalance, constitutes abuse and may affect Carrier warranty. See Unbalanced 3-Phase Supply Voltage, page 7.

Power Wiring Ð All power wiring must comply with applicable local and national codes. Install ®eld-supplied branch circuit fused disconnect(s) per NEC (National Electrical Code, U.S.A.) of a type that can be locked OFF or OPEN. Dis- connect(s) must be within sight from and readily accessible from unit in compliance with NEC Article 440-14.

GENERAL WIRING NOTES

1.A crankcase heater is wired in the control circuit so it is always operable as long as power supply disconnect is on, even if any safety device is open or unit stop-start switch is off. It is protected by a 5-amp circuit breaker in control power.

2.The power circuit ®eld supply disconnect should never be open except when unit is being serviced or is to be down for a prolonged period. When operation is resumed, crank- case heater should be energized for 24 hours before start- up. If unit is to be shut down for a prolonged period, it is recommended that the suction and discharge valves be

closed to prevent an excessive accumulation of refriger- ant in the compressor oil.

3.Power entry is one end only.

4.Maximum ®eld wire sizes allowed by lugs on terminal block are:

UNIT

V-Ph-Hz

WIRE

38AKS

SIZE*

 

028

208/230-3-60

 

034

208/230-3-60

 

230-3-50

350 kcmil

 

044

208/230-3-60

 

230-3-50

 

 

 

LEGEND

 

 

AWG Ð American Wire Gage kcmil Ð Thousand Circular Mils

*All other units use 2/0 AWG (67.4 mm2).

5.Terminals for ®eld power supply are suitable for copper, copper-clad aluminum, or aluminum conductors. Insula- tion must be rated 167 F (75 C) minimum.

CONDENSER FANS Ð The fans must rotate counterclock- wise when viewed from above. If necessary, correct direc- tion of fan rotation by interchanging any 2 power input wires at disconnect switch. Affix crankcase heater decal (located in installer's packet) to unit disconnect switch.

Table 3 Ð Electrical Data

60 HZ

 

UNIT

 

 

UNIT

 

 

 

 

COMPRESSOR

FAN MOTORS

 

Volts

Supplied*

 

 

 

MOCP

 

 

 

 

 

38AKS

 

MCA

 

ICF

RLA

LRA

FLA (ea)

Qty

3 Ph, 60 Hz

Min.

Max.

 

 

(Fuse)

 

 

 

 

 

 

 

 

 

 

 

 

 

500

208/230

187

254

 

124.6

 

200

452.2

89.8

446

6.2

2

028

 

200

380

342

418

 

64.7

 

110

250.9

45.5

247

3.9

2

 

600

460

414

508

 

60.7

 

100

226.1

43.6

223

3.1

2

 

 

 

 

 

 

100

575

518

632

 

52.5

 

80

167.4

36.5

164

3.4

2

 

 

500

208/230

187

254

 

145.5

 

250

512.2

106.5

506

6.2

2

034

 

200

380

342

418

 

72.5

 

125

283.9

52.6

280

3.9

2

 

600

460

414

508

 

68.7

 

110

256.1

50.0

253

3.1

2

 

 

 

 

 

 

100

575

518

632

 

54.9

 

90

179.4

38.5

176

3.4

2

 

 

500

230

187

254

 

203.0

 

350

702.4

147.5

690

6.2

3

044

 

200

380

342

418

 

111.1

 

175

389.8

79.5

382

3.9

3

 

600

460

414

508

 

91.0

 

150

351.2

65.4

345

3.1

3

 

 

 

 

 

 

100

575

518

632

 

81.5

 

125

282.8

57.1

276

3.4

3

 

 

 

 

 

 

 

 

50 HZ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

 

 

UNIT

 

 

 

 

COMPRESSOR

FAN MOTORS

 

Volts

Supplied*

 

 

 

MOCP

 

 

 

 

 

38AKS

 

MCA

 

ICF

RLA

LRA

FLA (ea)

Qty

3 Ph, 50 Hz

Min.

Max.

 

 

(Fuse)

 

 

 

 

 

 

 

 

 

 

 

 

 

800

230

198

254

 

109.0

 

175

348.4

76.9

342

6.4

2

028

 

300

346

311

380

 

64.9

 

100

263.4

44.9

259

4.4

2

 

 

900

400

342

400

 

60.5

 

100

226.0

43.6

223

3.0

2

 

 

800

230

198

254

 

120.2

 

200

372.4

85.9

366

6.4

2

034

 

300

346

311

380

 

76.1

 

125

298.4

53.9

294

4.4

2

 

 

900

400

342

400

 

68.5

 

110

256.0

50.0

253

3.0

2

 

 

800

230

198

254

 

150.6

 

250

557.8

105.1

545

6.4

3

044

 

300

346

311

380

 

112.6

 

175

408.8

79.5

400

4.4

3

 

 

900

400

342

400

 

90.8

 

150

351.0

65.4

345

3.0

3

 

LEGEND

CSA

Ð Canadian Standards Association

FLA

Ð Full Load Amps

ICF

Ð Maximum Instantaneous Current Flow during starting (the point

 

in the starting sequence where the sum of the LRA for the start-

 

ing compressor, plus the total FLA for all running fan motors is

 

maximum).

LRA

Ð Locked Rotor Amps

MCA

Ð Minimum Circuit Amps (complies with National

 

Electrical Code [NEC, U.S.A.], Section 430-24)

MOCP Ð Maximum Overcurrent Protection

RLA

Ð Rated Load Amps

UL

Ð Underwriters' Laboratories

*Units are suitable for use on electrical systems where voltage sup- plied to unit terminals is not below or above listed minimum and maxi- mum limits.

6

Page 6
Image 6
Carrier 38AKS028-044 dimensions Ð Electrical Data