J

 

RIGHT

SIDE PIPING

CONNECTIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Carefully

 

remove

the tubing and the condensate drain tube

0 o2-P,

 

 

 

 

 

 

 

 

 

 

from the

 

shipping

 

brackets.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Be careful

 

not

to

bend or

 

kink

the tubing.

Gently

rotate

FAN COIL

 

 

 

 

 

 

 

 

 

 

 

 

2.

 

 

UNIT

/

 

 

 

 

 

 

 

 

 

 

 

 

the

tubing

 

180

degrees.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

_2 W_TYP

3.

Using

a hand

tube

bender,

carefully

bend

the

 

tube ends

SCREW

 

 

 

 

 

 

 

 

 

 

 

 

DIA

 

 

until

they

coincide

with the

raceway

 

opening.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4. Carefully position the indoor section onto the wall bracket.

NOTE: Use either point "A" or point "B."

 

 

 

 

 

 

 

Be sure the tubing and dram tube are routed through the

 

 

 

 

 

 

 

piping hole in the wall.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 8 --

Wall Hole Location

For Fan Coil Unit

5.

Check that the indoor section

is mounted

 

level

to

ensure

 

 

 

Rear Piping (Size 009 Shown)

 

 

 

proper

condensate

 

drainage

and to

avoid

possible

water

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

damage. Be sure the drain tube is sloped toward the out-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

side and is not kinked

or

bent.

Ensure

that any drain ex-

 

 

 

 

 

 

 

 

-." i

":

 

 

 

 

 

 

tension is made outside the wall.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEFT

SIDE

 

PIPING

 

CONNECTIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Place

indoor

unit

on

wall

 

bracket.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.

Mark

where

the

tube flare connection

points

end

on

the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

wall.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.

Remove

the

indoor

section

from

the

wall

bracket.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.

Route

the

interconnecting

 

tubing

and

the

drain tube

ex-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tension through the wall sleeve.

 

 

 

 

 

 

 

 

 

 

 

 

(INDOORSIDE)

I

"

WALL .

I (OUTDOOR SIDE)

5.

Using

a hand

tube

bender,

 

carefully

bend

the

tubes until

NOTE:Slopecondensatelineat a minimumpitchof % in. perfoot.

 

they coincide with the position of the flare connection points

 

on the

wall.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig.

9 --

Piping

Hole

 

 

 

 

 

6.

Secure

indoor

section

to

the

wall

bracket.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.

Connect

the

drain

tube extension

to

the

condensate

drain

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tube.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Step

5 --

Connect

Refrigerant

Piping

--

 

Refer

8.

Carefully

 

position

the

indoor

section

onto

the wall bracket.

to Tables 4A-4D

for

correct piping sizes. The length of re-

 

Be

sure

the

tubing

and the drain tube are routed through

frigerant

pipe depends

on

the

unit

placement

 

and

building

 

the

piping

 

hole

in the

wall.

 

 

 

 

 

 

 

 

 

 

 

structure

--

run pipes

 

as

directly

as possible.

Piping

lengths

9.

Check

that

the

indoor

section

is mounted

 

level,

to

ensure

must

not

exceed

35

ft

of

total

run.

 

 

 

 

 

 

 

proper

condensate

 

drainage

and to

avoid

possible

water

 

 

 

 

 

I_?q[,]E_lldIi]_

 

 

 

 

 

 

damage. Be sure the drain tube is sloped toward the out-

 

 

 

 

 

 

 

 

 

 

 

side and is not kinked

or

bent.

Ensure

that any

drain

ex-

DO NOT BURY MORE THAN 36 IN. OF REFRIG-

 

tension is made outside the wall.

 

 

 

 

 

 

 

 

 

ALL TYPES

PIPING

CONNECTIONS

 

 

 

 

 

 

 

 

ERANT PIPE IN THE GROUND. lfany section of pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is buried,

there

must

be a 6-in.

vertical

rise

to the

valve

NOTE:

After

tubing

is routed

 

through

wall sleeve,

 

install

the

connections on the outdoor unit. If more than the rec-

factory-supplied

 

wall

cap

around

tubing

components

and into

ommended

length

is buried,

refrigerant

may

migrate

to

 

the

2V2-in. hole.

Do

 

not

fill

air

gaps

yet

with insulation

or

cooler,

buried

section

during

 

extended

periods of

unit

caulking

as

this

space

is helpful

when

connecting

 

tubing

to

shutdown,

causing

refrigerant

slugging and possible com-

outdoor

unit,

and

routing

electrical

power

supply.

 

Be

sure to

pressor

damage

at

start-up.

 

 

 

 

 

 

 

 

fill

air

spaces

ailer

installation

 

is

complete.

 

 

 

 

 

 

If it has not yet been removed, remove indoor section front panel by removing the Phillips head screws located at the bottom of the air outlet. It may be necessary to rotate the louvers to locate the mounting screws.

Make piping connections:

NOTE: Right rear piping connections are the preferred configuration.

RIGHT REAR AND BOTTOM PIPING CONNECTIONS

1.Carefully separate the tubing and condensate drain tube from the shipping brackets.

2.Be careful not to bend or kink the tubing. Gently rotate the tubing 90 degrees.

3.Carefully p°siti°n the ind°°r secti°n °nt° the wail bracket" Be sure the tubing and drain tube are routed through the piping hole in the wall.

4.Check that the indoor section is mounted level to ensure proper condensate drainage and to avoid possible water damage. Be sure the drain tube is sloped toward the out- side and is not kinked or bent. Ensure that any drain ex- tension is made outside the wall.

IMPORTANT: All refrigerant lines must be insulated because the refrigerant flow device is located in the outdoor section.

Run liquid and suction refrigerant piping.

1.Run pipes as directly as possible, avoiding any armec- essary turns and bends.

2.Suspend refrigerant pipes s° that the insulati°n is n°t darn"

aged and vibrations are not transmitted to the structure.

3.Leave slack in refrigerant pipe between the structure and the indoor and outdoor sections to absorb vibration.

Step 6 --Make Piping Connections

NOTE: The outdoor section must be connected to the indoor section using field-supplied tubing.

To make connections:

1.Unpack factory-supplied tubing package. Unwind tubing carefully. Do not bend or kink tubing.

10

Page 10
Image 10
Carrier 38AN,BK specifications Wall Hole Location For Fan Coil Unit, Rear Piping Size 009 Shown, ?q,ElldIi

38AN,BK specifications

The Carrier 38AN,BK is a distinguished model in the world of air conditioning, known for its advanced features, innovative technologies, and exceptional performance. This air conditioning unit is particularly favored for residential and small commercial applications, offering a perfect blend of efficiency, reliability, and comfort.

One of the main features of the Carrier 38AN,BK is its high energy efficiency, which is crucial in today’s eco-conscious environment. With a Seasonal Energy Efficiency Ratio (SEER) rating that often exceeds industry standards, this unit ensures minimal energy consumption while providing powerful cooling capabilities. This not only contributes to lower utility bills but also reduces the overall carbon footprint.

The Carrier 38AN,BK employs advanced cooling technologies that make it a standout choice. One notable feature is its use of a scroll compressor, which operates with fewer moving parts than traditional models, resulting in reduced noise levels and enhanced durability. This compressor design also ensures a smoother operation, translating to consistent temperature control and a more comfortable indoor environment.

Another innovative technology incorporated in the Carrier 38AN,BK is the use of smart controls, allowing users to easily adjust settings and monitor performance through compatible smart devices. This feature adds convenience and flexibility, enabling homeowners to manage their home climate efficiently, even when they are away.

In terms of construction, the Carrier 38AN,BK’s robust design includes a galvanized steel cabinet that is resistant to corrosion and designed to withstand adverse weather conditions. This ensures longevity and reliable performance throughout the year. Additionally, the unit features advanced filtration systems that help improve indoor air quality by reducing allergens and pollutants, further enhancing user comfort.

Furthermore, the Carrier 38AN,BK is designed to operate quietly, making it an ideal choice for bedrooms and other quiet spaces. Its noise reduction features, combined with its energy-saving capabilities, position it as an attractive choice for a wide range of applications.

In summary, the Carrier 38AN,BK air conditioning unit excels in efficiency, advanced technologies, and user-friendly features. Its reliable design and quiet operation make it a top choice for anyone seeking effective and environmentally responsible cooling solutions. As both technology-savvy and eco-friendly, it meets the demands of modern homeowners while delivering exceptional comfort year-round.