will stop30secondsafterthecompressorstopsAfter.
3
3.Whentheroomtemperatureisequaltoorgreaterthan 4°Fbelowtheselectedtemperature,thesystemoperates asfollows:Thecompressorandoutdoorfanoperatefor
for30secondsThe. normal dehumidification operation is
repeated for the newly sensed room temperature. If the room temperature is still 4° F below the selected tem- perature, the compressor, outdoor fan, and indoor fan re- main off. After 7_A minutes, the indoor fan operates at
•Heat Pump Heating Mode (Heat Pump Systems Only)
The compressor cannot run for 3 minutes from the time the system starts up or for 3 minutes from the time it last operated. When the temperature of the room is 8 ° F below the selected temperature, the unit will operate in Heat Pump mode until the temperature is 6° F above the selected tem- perature, or the compressor runs for 40 minutes (which- ever comes first). If the temperature of the room is less than 7 ° F below or equal to the selected temperature, the unit operates in Heat Pump mode until the selected set point temperature plus 2 ° F is reached.
•Electric Heat in Heat Pump Heating Mode (40QNH012 Heat Pump Unit Only)
NOTE: Electric heat control cannot be overridden.
•Demand Defrost Mode (Heat Pump Systems Only)
•Sleep Mode
can be selected are 1, 2, 3, or 7 hours. After the initial 30 minutes, the user set point shifts approximtely 1° F warmer. This sequence repeats itself every 40 minutes up to a total
of 150 minutes. When Sleep mode is enabled, the display on the remote controller is dimmed.
•ON/OFF Timer Mode
unit on or off at a user selectable on and off time (this is one time event only). The unit will start in the same mode and at the same selected temperature as when the system shut off. If the room temperature is not within approxi-
mately 5 ° F of the set point 40 minutes before
achieve the set point temperature at
•Automatic Operation Mode for Cooling Only Systems
1.Cooling Mode
82.4F with a preset temperature of 78.8 F.
2.Dry Mode
75.2F and less than 82.4 F with a preset temperature of 77 F.
3.Fan Only Mode
75.2E
The preset temperature can be changed by
•Automatic Operation Mode for Heat Pump Systems
•Test Mode
the slide switch on the fan coil unit to TEST position. The slide switch is located on the front of the unit as shown in
Fig. 17. The fan coil unit will start immediately (there is no compressor time delay when using Test mode) in Cool- ing mode with an infinitely low set point. The indoor fan speed will be at the high setting, and the swing louvers will be on (moving up and down).
NOTE: The unit cannot be controlled by the remote con- troller until the slide switch is returned to the REMOTE
position.
•Emergency Mode
1.Operation mode: AUTO.
2.Fan speed: AUTO.
3.Cooling set point: 77 F
4.Timer mode: Continuous
NOTE: The unit cannot be controlled by the remote con- troller until the slide switch is returned to the REMOTE
position.