Table 5 -- System Piston Guide and
Refrigerant Charges
UNIT | INDOOR | OUTDOOR | REQUIRED | ||
SYSTEM | |||||
|
| PISTON | PISTON | ||
|
| CHARGE | |||
Indoor | Outdoor | SIZE | SIZE | ||
(Ib)* | |||||
|
|
|
| ||
40QNB009 | 38AN009 | Capillary Tube | Capillary Tube | 1.50 | |
40QNB012 | 38AN012 | Capillary Tube | Capillary Tube | 180 | |
40QNEO09 | 38BK009 | 321" | 30t | 150 | |
40QNH012 | 38BK012 | 421" | 42"_ | 2.00 |
*Charge is based on25 f_of interconnectingtubing. Charge may need
to be added for longer tubing runs or when used with certain fan coils. Check unit nameplate for required charge. This is a total sys-
tem charge.
POSSIBLE PIPING DIRECTIONS
RIGHT
SIDE
LEFT
SIDE
KNOCKOUT
BoTroM KNOCKOUT
PREPUNGHED HOLES
FOR LEFT
SIDE PIPING
FOR RIGHT
SIDE PIPING FOR
PIPING
Fig. 5 -- Fan Coil Unit Refrigerant Piping
\
Jlllll!_'':ilj=*:'=*="0:_ !: ": : --H" ": -':::- :=:l_
FAN COIL
UNIT BOTI OM
BACK VIEW
35" MAX (FOR COOLING ONLY AND
HEAT PUMP SYSTEMS)
"_1_ | UNIT |
30" |
|
MAX |
|
INDOOR ELEVATION | INDOOR |
UNIT | IT |
// H//////H | |
OUTDOOR |
|
UNIT | ROOFTOP |
INSTALLATION | INSTALLATION |
Fig, 6 -- Maximum System Line Lengths
Step 4
1.If outdoor section is to be installed at ground level, mount
on a solid, level support pad one in. longer and one in. wider than the outdoor section dimensions.
2.Provide sufficient clearance for airflow, wiring, refriger-
ant piping, service and maintenance. Provide a minimum clearance of 2 ft from obstructions in front of outdoor
section, 2 ft on outdoor coil side, and 2_A ft on electrical and piping side. If more than one outdoor section is in- stalled, provide a minimum clearance of 2 ft between sec- tions. Position outdoor section so that water or ice from
roof cannot fall directly on unit.
NOTE: The outdoor section can be installed higher than, lower than, or level with the elevation of the indoor section. If outdoor section is mounted higher than the in- door section, the vertical distance between the 2 units should not exceed 30 i_. If the outdoor section is installed
lower than indoor section, the vertical distance between the units should not exceed 16 ft. See table below:
MAXIMUM DISTANCE BETWEEN OUTDOOR UNITS
Outdoor | Section | Higher | 30 | Ft Maximum | |
Than | Indoor Section |
| (Vertical) | ||
Outdoor | Section | Lower | 16 | Ft Maximum | |
Than | Indoor Section |
| (Vertical) |
NOTE: Maximum system piping length between indoor and outdoor units is 35 ft.
TOP HOLES | / |
FRONT VIEW
Fig. 7