Carrier 38AN,BK specifications 40QN Thermistor Properties, Troubleshooting, 265,444

Models: 38AN,BK

1 30
Download 30 pages 50.49 Kb
Page 21
Image 21
Table 11 --40QN Thermistor Properties*

Table 11 --40QN Thermistor Properties*

 

 

 

 

MINIMUM

NOMINAL

MAXIMUM

TEMP

MINIMUM

NOMINAL

MAXIMUM

THERMISTOR

THERMISTOR

THERMISTOR

(F)

OHMS

OHMS

OHMS

VOLTS --DC

VOLTS --DC

VOLTS --DC

-40

303,300

342,700

356,200

4.80

4.82

4.84

-30

211,500

237,276

265,444

4.72

4.75

4.77

-20

149,721

166,689

185,146

4.61

4.65

4.68

-10

107,379

118,776

130,973

4.48

4.52

4.55

0

77,281

85,677

93,867

4.30

4.35

4.40

10

56,567

62,617

65,205

4.09

4.16

4.21

20

42,661

46,302

50,129

3.86

3.92

3.98

39

32,043

34,580

37,220

3.59

3.66

3.72

32

30,300

32,550

35,120

3.53

3.60

3.66

49

24,061

26,118

27,960

3.28

3.36

3.43

50

18,650

19,900

21,180

2.99

3.05

3.11

60

14,402

15,312

16,219

2.67

2.73

2.79

70

11,247

11,883

12,518

2,36

2.42

2.47

80

8,820

9,299

9,779

2.06

2.11

2.16

90

6,846

7,339

7,754

1.76

1.83

1.58

100

5,487

5,529

6,187

1,52

1,57

1.63

110

4,367

4,667

4,976

1.29

1.34

1,40

120

3,502

3,760

4,026

1.09

1.14

1,19

130

2,830

3,051

3,281

0.92

0.97

1,02

140

2,300

2,489

2,687

0.77

0.82

0,87

150

1,880

2,045

2,216

0.65

0.69

0.74

160

1,547

1,688

1,836

0.55

0.59

0.63

170

1,280

1,402

1,531

0.46

0,50

0.53

180

1,065

1,170

1,282

0.39

0.42

0.45

190

690

982

1,078

0.33

0.36

0.39

299

748

828

913

0.28

0.31

0.33

210

631

701

766

0.24

0.26

0.28

212

611

678

751

0.23

0.25

0.28

"Circuit volts = 5 vdc.

Table 12 -- Troubleshooting

PROBLEM

POTENTIAL

SOURCE

ACTION

 

Circuit breaker has tripped or fuse is blown

Reset the circuit breaker or replace the fuse.

Unit does not

Power failure

 

Restart fun coil unit operation when power is restored.

operate

Voltage is too low

 

Confirm the available voltage.

 

 

 

Air filter is blocked with dust

 

Clean the air filter.

 

Temperature is not set properly

Check and reset if necessary.

Insufficient

Window(s) and/or door(s) are open

Close window(s) and door(s).

Cooling

Outdoor unit is obstructed

 

Remove the obstruction.

 

Fan speed is too low

 

Change the fan speed

 

Operation mode is set to fan

or auto. mode

Change to cooling operation or reset temperature

 

(using remote controller).

 

Air filter is blocked with dust

 

Clean the air filter.

Insufficient

Temperature is not set properly

Check and reset if necessary.

Heating*

Window(s) and/or door(s) are open

Close window(s) and door(s).

 

Outdoor unit is obstnJcted

 

Remove the obstruction.

Unit stops

Off timer is operating

 

Turn off the off timer function.

during operation

Room temperature has reached the programmed set point

Normal unit operation.

*Heat pump systems only.

2)