Complete the following checks and the
1. Check condensate drainage system. Refer to Fig. 4 and 10. Add water to check the drainage flow. If water does not flow steadily, check the pipe slope or see if there are any restrictions.
2.Make sure all wiring connections are correct and tight.
3.Be sure all barriers, covers, and panels are in place.
4.Ensure that the filters have been installed and that the air discharge louvers are correctly positioned.
Never operate unit without a filter. Damage to the unit could result.
5.Fully backseat (open) the liquid and vapor tube service valves.
6.Unit is shipped with valve stems frontseated and caps fac- tory installed. Replace stem caps after system is opened to refrigerant flow (backseated). Replace caps finger fight.
7.With the remote controller, turn on the unit and operate in each mode (as applicable) for 15 minutes to test for proper operation. Do not operate in Cooling mode if out- door temperature is below 55 F, unless unit is equipped with low ambient control. Do not operalg in Heating mode
(heat pump systems only) if the outdoor temperature is above 75 F.
8.Test forproper refrigerant charge using the superheat method.
9.Explain basic system operation to the owner.
40QN Control System
with a microprocessor control which operates the system.
This control is located in the control box of the fan coil unit, with thermistors located in the fan coil inlet and on the in-
door coil. The 40QNE/H heat pump fan coil units also have thermistors located on the outdoor coil and in the outdoor air
inlet. These thermistors monitor system operation and con- trol the operating mode. To change settings or modes of op-
eration, use the
Wireless Remote Controllers
controller is supplied for system operation of all high
wall units. Each
REMOTE
BRACKET
Fig. 13 -- Mounting Remote Controller Bracket
communication, all of the following must be true for the con- troller to work properly:
1.The power must be on to the fan coil unit.
2.The batteries in the controller must be good.
3.The controller must be within range of and pointed di- rectly at the fan coil unit.
4.The fan coil unit's
The remote controller includes a
After Extended
Seasonal
fore starting cooling only system after it has been out of use
for the winter season, perform the following steps BEFORE starting the system:
1.Inspect and clean the outdoor unit, particularly the coil.
2.Clean or replace the air filters in the indoor unit.
3.Clean the indoor unit drain pan and drain pipe, and re- move any obstructions.
4.Turn on the indoor and outdoor unit disconnect switches
to supply power to the system for 12 hours before start- ing the system.
To Turn the Unit On and Off
Adjusting Airflow
it is recommended that the air discharge louvers be set to discharge vertically (see Fig. 15).
The Swing Range shown in Fig. 15 is the range which will provide maximum occupant comfort in each mode. It is recommended that the louvers be positioned within this range (using the remote controller).
NOTE: The full swing range for the selected mode will au- tomatically be used if auto. fan mode is selected.
Operating Mode
Automatic Operation (Auto.)
NOTE: Between the cooling cycle and the heating cycle there is a neutral zone of approximately 2 ° F above and 2 ° F be-
low the selected temperature when only the fan is operating.
14