A-11

A-11

INSTALLATION

Figure A.1

CONNECTION OF RANGER 8 TO PREMISES WIRING

 

 

 

230 VOLT

 

 

 

 

 

 

 

 

 

 

 

GROUNDED CONDUCTOR

230 Volt￿

 

POWER￿

 

 

115 VOLT

 

￿

 

 

60 Hz.￿

 

 

 

 

 

 

 

 

COMPANY￿

 

 

 

 

 

 

3-Wire￿

 

 

115 VOLT

 

 

 

￿

 

 

 

Service

 

 

 

 

 

METER

 

 

 

 

 

 

 

 

 

 

 

 

 

NEUTRAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BUS

N

LOAD

DOUBLE POLE DOUBLE THROW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SWITCH RATING TO BE THE SAME

 

 

 

 

 

 

 

 

 

 

 

AS OR GREATER THAN PREMISES

 

 

 

 

 

 

 

 

 

 

 

SERVICE OVERCURRENT

 

 

 

 

 

 

 

 

 

 

 

PROTECTION.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PREMISES￿

 

 

 

 

 

 

 

 

 

 

 

DISCONNECT AND￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SERVICE￿

 

 

 

GROUND

 

 

35AMP￿

OVERCURRENT￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PROTECTION

 

 

230 VOLT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOUBLE￿

50 AMP, 115/230￿

 

POLE￿

 

CIRCUIT￿

VOLT PLUG￿

230 VOLT

BREAKER

NEMA TYPE 14-50

 

 

GND

N

50 AMP, 115/230 VOLT￿

RECEPTACLENOTE: No. 8 COPPER CONDUCTOR CABLE SEE￿

NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE￿

SIZE RECOMMENDATIONS.

WARNING

Connection of Ranger 8 to premises wiring must be done by a licensed electrician and must comply with the National Electrical Code and all other applicable electrical codes.

RANGER 8

Page 17
Image 17
Lincoln Electric SVM107-B service manual Figure A.1, Connection of Ranger 8 to Premises Wiring