48SS048,060 WITH OPTIONAL BASE RAIL
REQ'D CLEARANCES FOR SERVICING. in. (mm) |
|
|
|
|
Duct panel | . | . . . . 0 | ||
Unit top | . | . 36 | (914) | |
Side opposite ducts | . | . 36 | (914) | |
Compressor access | . | . 36 | (914) | |
(Except for NEC requirements) |
|
|
|
REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)
Maximum extension of overhangs |
| . . . . . . 48 (1219) | |||||
Unit top | . | . . . . . | . 14 | (356) | |||
Duct side of unit | . | . | . . | . | . . . 2 (51) | ||
Side opposite ducts | . | . | . . | . | . | . 14 | (356) |
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . 0
Flue panel . . . . . . . . . . . . . . . . . . . . . 36 (914)
NEC REQ'D CLEARANCES. in. (mm) |
|
|
|
|
|
Between units, control box side | . | . | . 42 | (1067) | |
Unit and ungrounded surfaces, control box side . . | . | . . | . 36 (914) | ||
Unit and block or concrete walls and other grounded |
|
|
|
| |
surfaces, control box side | . | . | . 42 | (1067) |
UNIT | ELECTRICAL | UNIT WEIGHT |
| CORNER WEIGHT (lb/kg) |
| ||
| CHARACTERISTICS | lb | kg | A | B | C | D |
48SS048080 | 438 | 199 | 113/51 | 89/40 | 164/75 | 72/33 | |
48SS048100/120/140 | 450 | 205 | 116/53 | 92/42 | 165/75 | 77/35 | |
48SS060080 | 477 | 217 | 123/56 | 99/45 | 173/79 | 82/37 | |
48SS060100/120/140 | 489 | 222 | 126/57 | 102/46 | 173/79 | 88/40 |
UNIT | CENTER OF GRAVITY (in./mm) | ||
| X | Y | Z |
48SS048080 | 28.54/724.9 | 20.00/508 | 17.66/448.6 |
48SS048100/120/140 | 28.22/716.8 | 20.05/509.3 | 17.66/448.6 |
48SS060080 | 28.18/715.6 | 20.19/512.8 | 17.66/448.6 |
48SS060100/120/140 | 27.79/705.9 | 20.23/513.8 | 17.66/448.6 |
|
| LEGEND |
|
| |
CG | Ð | Center of Gravity | MAT'L | Ð | Material |
COND | Ð | Condenser | NEC | Ð | National Electrical Code |
LV | Ð | Low Voltage | REQ'D | Ð | Required |
NOTES:
1.Clearances must be maintained to prevent recirculation of air from
2.Adequate clearance around air openings into combustion chamber must be provided.
11