ARI* capacities

COOLING CAPACITIES AND EFFICIENCIES

UNIT 48SS

NOMINAL

STANDARD

NET COOLING²

SEER²

SOUND RATINGS**

TONS

CFM

CAPACITIES

(Bels)

 

 

018040

11¤2

600

17,000

10.0

7.4

024040

2

800

24,000

10.0

7.6

024060

 

 

 

 

 

030040

 

 

 

 

 

030060

21¤2

1000

29,200

10.0

8.0

030080

 

 

 

 

 

036060

 

 

 

 

 

036080

3

1200

36,000

10.0

8.0

036100

 

 

 

 

 

036120

 

 

 

 

 

042060

 

 

 

 

 

042080

31¤2

1400

42,500

10.0

8.2

042100

042120

 

 

 

 

 

048080

 

 

 

 

 

048100

4

1600

47,000

10.0

8.2

048120

 

 

 

 

 

048140

 

 

 

 

 

060080

 

 

 

 

 

060100

5

1995

59,500

10.0

8.2

060120

 

 

 

 

 

060140

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

Bels

Ð Sound Levels (1 bel = 10 decibels)

db

Ð Dry Bulb

SEER Ð

Seasonal Energy Efficiency Ratio

wb

Ð

Wet Bulb

*Air Conditioning & Refrigeration Institute.

²Rated in accordance with U.S. Government DOE (Department of Energy) test procedures and/or ARI Standard 210/240.

**Rated in accordance with ARI Standard 270.

NOTES:

1.Capacity ratings are net values, re¯ecting the effects of circulating fan heat.

Ratings are based on:

Cooling Standard: 80 F db, 67 F wb indoor entering-air tempera- ture and 95 F db outdoor entering-air temperature.

2.Before purchasing this appliance, read important energy cost and ef- ®ciency information available from your retailer.

OUTDOOR SOUND: ONE-THIRD OCTAVE BAND DATA Ð DECIBELS

FREQUENCY (Hz)

 

 

 

UNIT 48SS

 

 

 

018

024

030

036

042

048

060

 

63

49.8

38.1

45.7

47.8

45.5

56.0

54.3

125

56.5

55.0

58.1

59.3

61.2

65.6

65.1

250

60.3

65.3

68.7

67.4

70.4

71.5

71.5

500

59.8

67.2

64.7

68.8

69.9

71.4

72.7

1000

64.1

68.9

73.0

73.1

76.5

74.2

73.9

2000

64.1

65.5

70.2

69.5

71.3

73.3

73.4

4000

65.2

63.8

68.8

68.2

73.7

69.6

71.7

8000

56.0

60.3

66.6

65.8

65.5

67.1

66.3

Bels Ð Sound Levels (1 bel = 10 decibels)

4

Page 4
Image 4
Carrier 48SS ARI* capacities, Cooling Capacities and Efficiencies, Outdoor Sound ONE-THIRD Octave Band Data Ð Decibels