COOLING CAPACITIES (cont)

48SS048

TEMP (F)

 

 

EVAP AIR Ð CFM/BF

 

 

1400/0.08

 

1600/0.10

 

1800/0.11

AIR ENT

 

 

 

 

 

Evap Air Ð Ewb (F)

 

 

 

COND

 

 

 

 

 

 

 

 

62

67

72

 

62

67

72

 

62

67

72

 

TC

43.8

48.3

52.9

 

44.5

49.1

53.7

 

45.1

49.6

53.9

85

SHC

39.4

32.7

25.6

 

41.9

34.6

26.4

 

44.1

36.4

27.1

 

kW

4.76

4.85

4.95

 

4.87

4.97

5.07

 

4.99

5.08

5.17

 

TC

41.9

46.4

50.9

 

42.6

47.0

51.7

 

43.3

47.5

52.2

95

SHC

38.6

32.1

24.8

 

41.1

33.9

25.9

 

43.1

35.9

26.8

 

kW

5.17

5.28

5.38

 

5.29

5.40

5.50

 

5.41

5.51

5.61

 

TC

39.3

44.2

48.8

 

40.1

44.7

49.2

 

41.2

45.2

49.6

105

SHC

37.3

31.2

24.1

 

39.7

33.1

25.1

 

41.2

35.1

26.0

 

kW

5.61

5.73

5.83

 

5.74

5.85

5.95

 

5.87

5.96

6.06

 

TC

36.6

41.5

46.4

 

37.7

42.4

47.0

 

39.0

42.8

47.4

115

SHC

35.9

30.2

23.4

 

37.6

32.4

24.3

 

39.0

34.2

25.4

 

kW

6.08

6.22

6.34

 

6.22

6.34

6.45

 

6.36

6.46

6.57

 

 

LEGEND

BF

Ð Bypass Factor

edb

Ð Entering Dry-Bulb

Ewb

Ð Entering Wet-Bulb

kW

Ð Total Unit Power Input

ldb

Ð

Leaving Dry-Bulb

lwb

Ð

Leaving Wet-Bulb

SHC Ð Sensible Heat Capacity, 1000 Btuh

TC

Ð Total Cooling Capacity, 1000 Btuh (net)

NOTES:

1.Ratings are net; they account for the effects of the indoor-fan motor power and heat.

2.Direct interpolation is permissible. Do not extrapolate.

3.The following formulas may be used:

tldb = tedb ± sensible capacity (Btuh)

1.10x cfm

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving indoor coil (hlwb)

hlwb = hewb ± total capacity (Btuh) 4.5 x cfm

48SS060

TEMP (F)

 

 

EVAP AIR Ð CFM/BF

 

 

1750/0.03

 

2000/0.04

 

2250/0.05

AIR ENT

 

 

 

 

 

Evap Air Ð Ewb (F)

 

 

 

COND

 

 

 

 

 

 

 

 

62

67

72

 

62

67

72

 

62

67

72

 

TC

55.0

62.0

69.4

 

56.3

63.1

70.5

 

58.2

63.9

71.3

85

SHC

52.4

43.7

34.2

 

56.1

46.7

35.8

 

58.1

49.5

37.4

 

kW

6.14

6.33

6.53

 

6.32

6.50

6.70

 

6.52

6.67

6.88

 

TC

51.8

58.8

66.2

 

53.6

59.6

67.3

 

55.6

60.2

68.1

95

SHC

51.0

42.4

33.2

 

53.5

45.3

34.8

 

55.6

48.2

36.3

 

kW

6.62

6.82

7.05

 

6.83

7.00

7.22

 

7.03

7.17

7.39

 

TC

48.7

55.1

62.9

 

51.0

56.0

63.9

 

53.0

56.7

64.5

105

SHC

48.7

41.1

32.1

 

50.9

44.0

33.7

 

52.8

46.9

35.3

 

kW

7.17

7.37

7.60

 

7.39

7.54

7.78

 

7.59

7.71

7.95

 

TC

45.8

52.0

59.5

 

48.5

52.8

60.5

 

50.4

53.4

60.8

115

SHC

45.8

40.0

30.9

 

48.4

42.8

32.6

 

50.3

45.6

34.1

 

kW

7.77

7.94

8.19

 

7.98

8.12

8.36

 

8.18

8.29

8.43

Where: hewb = Enthalpy of air entering indoor coil

4.The SHC is based on 80 F edb temperature of air entering indoor coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 ± BF) x (edb ± 80).