Electrical data

 

 

VOLTAGE

 

 

COND

INDOOR

 

 

AWG 60 C

MAX WIRE

UNIT

 

COMPRESSOR

FAN

POWER SUPPLY

V-PH-HZ

RANGE

FAN

MIN WIRE

LENGTH

48SS

 

 

MOTOR

 

 

 

 

 

 

 

 

 

 

SIZE²

(ft)

 

 

Min

Max

RLA

LRA

FLA

FLA

MCA

MOCP*

 

 

 

 

018

208/230-1-60

187

253

7.6

45

0.7

1.8

12.0

15

14

75

024

208/230-1-60

187

253

12.4

61

0.7

2.0

18.2

30

12

80

030

208/230-1-60

187

253

14.4

82

1.4

2.0

21.8

30

10

100

208/230-3-60

187

253

9.4

66

1.4

2.0

15.5

25

12

80

 

 

208/230-1-60

187

253

18.0

96

1.4

2.8

26.7

40

10

90

036

208/230-3-60

187

253

11.7

75

1.4

2.8

18.8

30

12

65

 

460-3-60

414

506

5.6

40

0.8

1.4

9.2

10

14

100

 

208/230-1-60

187

253

20.4

104

1.4

4.0

30.9

50

8

100

042

208/230-3-60

187

253

14.0

91

1.4

4.0

22.9

35

10

85

 

460-3-60

414

506

6.4

42

0.8

2.0

10.8

15

14

100

 

208/230-1-60

187

253

26.4

129

2.1

5.0

40.1

60

6

100

048

208/230-3-60

187

253

15.0

99

2.1

5.0

25.9

40

10

75

 

460-3-60

414

506

8.2

50

1.1

2.3

13.7

20

14

100

 

208/230-1-60

187

253

32.1

169

2.1

6.8

49.0

60

6

100

060

208/230-3-60

187

253

19.3

123

2.1

6.8

33.0

50

8

90

 

460-3-60

414

506

10.0

62

1.1

3.2

16.8

25

12

100

LEGEND

EXAMPLE: Supply voltage is 460-3-60.

AWG

Ð American Wire Gage

CSA

Ð CanadianStandards Association

FLA

Ð Full Load Amps

HACR

Ð Heating, Air Conditioning and

 

Refrigeration

LRA

Ð Locked Rotor Amps

AB = 452 v

BC = 464 v

AC = 455 v

Average Voltage =

452 + 464 + 455

3

1371

MCA

Ð Minimum Circuit Amps

MOCP Ð Maximum Overcurrent Protection

 

(fuses or HACR-type circuit breaker)

NEC

Ð National Electrical Code

RLA

Ð Rated Load Amps

*Fuse or HACR breaker.

²Minimum wire size is based on 60 C copper wire. If other than 60 C if used, determine size from NEC. Voltage drop of wire must be less than 2% of rated voltage.

=

3 = 457

Determine maximum deviation from average voltage. (AB) 457 ± 452 = 5 v

(BC) 464 ± 457 = 7 v

(AC) 457 ± 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

NOTES:

1. In compliance with NEC requirements for multimotor and combina-

% Voltage Imbalance = 100 x

7

tion load equipment (refer to NEC Articles 430 and 440), the over-

current protective device for the unit shall be fuse or HACR breaker.

The CSA units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is

greater than 2%. Use the following formula to determine the percent-

age of voltage imbalance.

% Voltage Imbalance

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

= 100 x

max voltage deviation from average voltage

average voltage

24