Electrical data
|
| VOLTAGE |
|
| COND | INDOOR |
|
| AWG 60 C | MAX WIRE | ||
UNIT |
| COMPRESSOR | FAN | POWER SUPPLY | ||||||||
RANGE | FAN | MIN WIRE | LENGTH | |||||||||
48SS |
|
| MOTOR |
|
| |||||||
|
|
|
|
|
|
|
| SIZE² | (ft) | |||
|
| Min | Max | RLA | LRA | FLA | FLA | MCA | MOCP* | |||
|
|
|
| |||||||||
018 | 187 | 253 | 7.6 | 45 | 0.7 | 1.8 | 12.0 | 15 | 14 | 75 | ||
024 | 187 | 253 | 12.4 | 61 | 0.7 | 2.0 | 18.2 | 30 | 12 | 80 | ||
030 | 187 | 253 | 14.4 | 82 | 1.4 | 2.0 | 21.8 | 30 | 10 | 100 | ||
187 | 253 | 9.4 | 66 | 1.4 | 2.0 | 15.5 | 25 | 12 | 80 | |||
| ||||||||||||
| 187 | 253 | 18.0 | 96 | 1.4 | 2.8 | 26.7 | 40 | 10 | 90 | ||
036 | 187 | 253 | 11.7 | 75 | 1.4 | 2.8 | 18.8 | 30 | 12 | 65 | ||
| 414 | 506 | 5.6 | 40 | 0.8 | 1.4 | 9.2 | 10 | 14 | 100 | ||
| 187 | 253 | 20.4 | 104 | 1.4 | 4.0 | 30.9 | 50 | 8 | 100 | ||
042 | 187 | 253 | 14.0 | 91 | 1.4 | 4.0 | 22.9 | 35 | 10 | 85 | ||
| 414 | 506 | 6.4 | 42 | 0.8 | 2.0 | 10.8 | 15 | 14 | 100 | ||
| 187 | 253 | 26.4 | 129 | 2.1 | 5.0 | 40.1 | 60 | 6 | 100 | ||
048 | 187 | 253 | 15.0 | 99 | 2.1 | 5.0 | 25.9 | 40 | 10 | 75 | ||
| 414 | 506 | 8.2 | 50 | 1.1 | 2.3 | 13.7 | 20 | 14 | 100 | ||
| 187 | 253 | 32.1 | 169 | 2.1 | 6.8 | 49.0 | 60 | 6 | 100 | ||
060 | 187 | 253 | 19.3 | 123 | 2.1 | 6.8 | 33.0 | 50 | 8 | 90 | ||
| 414 | 506 | 10.0 | 62 | 1.1 | 3.2 | 16.8 | 25 | 12 | 100 |
LEGEND |
EXAMPLE: Supply voltage is
AWG | Ð American Wire Gage |
CSA | Ð CanadianStandards Association |
FLA | Ð Full Load Amps |
HACR | Ð Heating, Air Conditioning and |
| Refrigeration |
LRA | Ð Locked Rotor Amps |
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
452 + 464 + 455
3
1371
MCA | Ð Minimum Circuit Amps |
MOCP Ð Maximum Overcurrent Protection | |
| (fuses or |
NEC | Ð National Electrical Code |
RLA | Ð Rated Load Amps |
*Fuse or HACR breaker.
²Minimum wire size is based on 60 C copper wire. If other than 60 C if used, determine size from NEC. Voltage drop of wire must be less than 2% of rated voltage.
=
3 = 457
Determine maximum deviation from average voltage. (AB) 457 ± 452 = 5 v
(BC) 464 ± 457 = 7 v
(AC) 457 ± 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
NOTES:
1. In compliance with NEC requirements for multimotor and combina- |
% Voltage Imbalance = 100 x
7
tion load equipment (refer to NEC Articles 430 and 440), the over- |
current protective device for the unit shall be fuse or HACR breaker. |
The CSA units may be fuse or circuit breaker. |
2. Unbalanced |
Never operate a motor where a phase imbalance in supply voltage is |
greater than 2%. Use the following formula to determine the percent- |
age of voltage imbalance. |
% Voltage Imbalance |
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
= 100 x
max voltage deviation from average voltage
average voltage
24