REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
| INCHES | [mm] |
TOP OF UNIT | 14.00 | [355.6] |
DUCT SIDE OF UNIT | 2.00 | [50.8] |
SIDE OPPOSITE DUCTS | 14.00 | [355.6] |
BOTTOM OF UNIT | 0.50 | [12.7] |
ELECTRIC HEAT PANEL | 36.00 | [914.4] |
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
| INCHES | [mm] |
|
EVAP. COIL ACCESS SIDE | 36.00 | [914.0] |
|
POWER ENTRY SIDE | 36.00 | [914.0] |
|
(EXCEPT FOR NEC REQUIREMENTS) |
|
|
|
UNIT TOP | 48.00 | [1219.2] |
|
SIDE OPPOSITE DUCTS | 36.00 | [914.0] |
|
DUCT PANEL | 12.00 | [304.8] | * |
NEC. REQUIRED CLEARANCES.
| INCHES | [mm] |
BETWEEN UNITS, POWER ENTRY SIDE | 42.00 | [1066.8] |
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 | [914.0] | |
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER |
|
|
GROUNDED SURFACES, POWER ENTRY SIDE | 42.00 | [1066.8] |
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 304.8 [12.00] FROM WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
C99006
|
| UNIT WEIGHT | UNIT HEIGHT |
| CENTER OF GRAVITY |
| |||
UNIT | ELECTRICAL CHARACTERISTICS | IN. [MM] |
|
| IN. [MM] |
| |||
|
|
|
|
| |||||
|
| lb | kg | "A" | X |
| Y |
| Z |
|
|
|
|
|
|
|
|
|
|
50JS048 | 353 | 160.1 | 38.98 [990.2] | 20.5 [520.7] |
| 20.6 [523.8] |
| 17.0 [431.8] | |
|
|
|
|
|
|
|
|
|
|
50JS060 | 418 | 189.6 | 38.98 [990.2] | 19.5 [495.3] |
| 19.8 [501.7] |
| 17.0 [431.8] | |
50JX042 | 350 | 158.8 | 40.98 [1040.9] | 21.0 [533.4] |
| 20.5 [520.7] |
| 16.6 [421.6] | |
|
|
|
|
|
|
|
|
|
|
50JX048 | 355 | 161.0 | 40.98 [1040.9] | 20.0 [508.0] |
| 21.3 [539.8] |
| 18.0 [457.2] | |
|
|
|
|
|
|
|
|
|
|
50JX060 | 428 | 194.1 | 42.98 [1091.7] | 21.0 [533.4] |
| 20.0 [508.0] |
| 17.6 [447.0] |
Fig. 3Ð50JS048-060/50JX042-060 Unit Dimensions