Table 5ÐCooling and Heating Troubleshooting Chart
SYMPTOM | CAUSE | REMEDY | |
| Power failure | Call power company | |
|
|
| |
| Fuse blown or circuit breaker tripped | Replace fuse or reset circuit breaker | |
|
|
| |
| Defective thermostat, contactor, transformer, con- | Replace component | |
| trol relay or defrost board | ||
|
| ||
|
|
| |
Compressor and outdoor fan will not start | Insufficient line voltage | Determine cause and correct | |
Incorrect or faulty wiring | Check wiring diagram and rewire correctly | ||
| |||
|
|
| |
| Thermostat setting too high | Lower thermostat setting below room tempera- | |
| ture | ||
|
| ||
|
|
| |
|
| DO NOT bypass this compressor time | |
| Units have a | delayÐwait for 5 min. until | |
|
| deenergized | |
| Faulty wiring or loose connections in compressor | Check wiring and repair or replace | |
| circuit | ||
|
| ||
|
|
| |
| Compressor motor burned out, seized, or internal | Determine cause | |
Compressor will not start but condenser fan | overload open | Replace compressor | |
|
| ||
Defective run capacitor, overload, or PTC (posi- |
| ||
runs | Determine cause and replace | ||
tive temperature coefficient) thermistor | |||
|
| ||
|
|
| |
| One leg of | Replace fuse or reset circuit breaker | |
| Determine cause | ||
|
| ||
|
|
| |
| Low input voltage (20% low) | Determine cause and correct | |
Scroll compressor is rotating in the wrong direc- | Correct the direction of rotation by reversing the | ||
060units) makes excessive noise, and there | |||
tion | |||
may be a low pressure differential | |||
|
| ||
|
|
| |
| Refrigerant overcharge or undercharge | Recover refrigerant, evacuate system, and re- | |
| charge to capacities shown on nameplate | ||
|
| ||
|
|
| |
| Defective compressor | Replace and determine cause | |
| Insufficient line voltage | Determine cause and correct | |
Compressor cycles (other than normally sat- | Blocked outdoor coil | Determine cause and correct | |
|
| ||
Defective run/start capacitor, overload or start |
| ||
isfying thermostat) | Determine cause and replace | ||
relay | |||
|
| ||
|
|
| |
| Defective thermostat | Replace thermostat | |
|
|
| |
| Faulty | Replace | |
| Damaged reversing valve | Determine cause and correct | |
|
|
| |
| Restriction in refrigerant system | Locate restriction and remove | |
|
|
| |
| Dirty air filter | Replace filter | |
| Unit undersized for load | Decrease load or increase unit size | |
| Thermostat set too low | Reset thermostat | |
|
|
| |
| Low refrigerant charge | Locate leak, repair, and recharge | |
| Leaking valves in compressor | Replace compressor | |
Compressor operates continuously |
| Check defrost time settings | |
| Frosted coil with incorrect defrost operation | Reset as necessary | |
| Check defrost temperature switch | ||
|
| ||
|
| Replace as necessary | |
|
|
| |
| Air in system | Recover refrigerant, evacuate system, and re- | |
| charge | ||
|
| ||
|
|
| |
| Outdoor coil dirty or restricted | Clean coil or remove restriction | |
|
|
| |
| Dirty air filter | Replace filter | |
| Dirty indoor or outdoor coil | Clean coil | |
| Refrigerant overcharged | Recover excess refrigerant | |
Excessive head pressure |
|
| |
Air in system | Recover refrigerant, evacuate system, and re- | ||
| charge | ||
|
| ||
|
|
| |
| (Heat) Indoor air restricted or recirculating | Determine cause and correct | |
|
|
| |
| Indoor or outdoor air restricted or air | Determine cause and correct | |
| Low refrigerant charge | Check for leaks, repair and recharge | |
Head pressure too low |
|
| |
Compressor valves leaking | Replace compressor | ||
|
|
| |
| Restriction in liquid tube | Remove restriction | |
| (Heat) Outdoor coil frosted | Move timer on control board to 30 min. between | |
| defrost cycles | ||
|
| ||
Excessive suction pressure | (Cool) High Heat load | Check for source and eliminate | |
Compressor valves leaking | Replace compressor | ||
| |||
|
|
| |
| Reversing valve hung up or leaking internally | Replace valve | |
| Refrigerant overcharged | Recover excess refrigerant | |
|
|
|
24