Carrier 50JS instruction manual BÐWet Coil Air Delivery, Unit 50JX 024-060Deduct 10% for

Models: 50JS

1 28
Download 28 pages 58.47 Kb
Page 18
Image 18

Table 4BÐWet Coil Air Delivery

Unit 50JX 024-060 (Deduct 10% for 208v)*

UNIT

MOTOR SPEED

 

 

 

EXTERNAL STATIC PRESSURE (IN. WG)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

Watts

275

273

271

270

-

-

-

-

-

-

-

 

Cfm

923

844

754

669

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

024

Med

Watts

-

-

-

359

353

350

347

341

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

Cfm

-

-

-

941

876

814

737

622

-

-

-

 

 

 

High

Watts

-

-

-

-

-

-

447

439

431

423

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cfm

-

-

-

-

-

-

968

869

765

659

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

Watts

276

276

272

-

-

-

-

-

-

-

-

 

Cfm

963

929

781

-

-

-

-

-

-

-

-

 

 

30

Med

Watts

375

377

371

362

354

350

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

Cfm

1202

1170

1079

976

884

807

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

Watts

-

-

-

-

469

449

435

428

-

-

-

 

Cfm

-

-

-

-

1174

988

828

718

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

Watts

462

451

431

411

394

381

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cfm

1374

1290

1205

1116

1020

916

-

-

-

-

-

 

 

36

Med

Watts

523

506

490

471

449

426

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

Cfm

1500

1408

1301

1190

1082

977

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

Watts

-

645

628

610

595

584

575

-

-

-

-

 

Cfm

-

1474

1369

1267

1169

1069

962

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

Watts

620

600

586

574

562

548

530

510

487

462

439

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cfm

1662

1621

1581

1540

1496

1447

1392

1331

1263

1186

1103

 

 

42

Med

Watts

-

-

-

-

686

661

634

606

577

547

517

Cfm

-

-

-

-

1722

1662

1594

1515

1427

1330

1227

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

Watts

-

-

-

-

-

-

-

757

730

704

682

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cfm

-

-

-

-

-

-

-

1669

1577

1486

1402

 

 

 

Low

Watts

620

600

586

574

562

548

530

-

487

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cfm

1662

1621

1581

1540

1496

1447

1392

1331

1263

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

48

Med

Watts

763

747

729

709

686

661

634

606

577

547

517

Cfm

1917

1868

1822

1774

1722

1662

1594

1515

1427

1330

1227

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

Watts

-

-

-

852

832

809

784

757

730

704

682

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cfm

-

-

-

1982

1914

1839

1757

1669

1577

1486

1402

 

 

 

Low

Watts

597

592

578

526

460

452

445

-

-

-

-

 

Cfm

2265

2190

2101

2033

1974

1869

1614

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

Med

Watts

754

730

707

687

671

658

646

630

603

558

486

Cfm

2383

2282

2202

2134

2070

2005

1935

1858

1771

1667

1576

 

 

 

High

Watts

901

876

856

836

813

785

755

723

696

681

687

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cfm

2480

2383

2301

2233

2175

2122

2066

1998

1910

1788

1619

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Air delivery values are based on operating voltage of 230 v or 460 v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain static pressure available for ducting.

NOTES:

1.Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below this point.

2.Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended. 3. Deduct 10% for 208v.

The charging label and the tables shown refer to system tempera- tures and pressures in cooling mode only. A refrigerant charging label is attached to the outside of the service access door. If charge level is suspect in Heating mode, reclaim all refrigerant and charge to nameplate amount. (This information may be obtained from the physical data table also.)

IMPORTANT: When evaluating the refrigerant charge, an indi- cated adjustment to the specified factory charge must always be very minimal. If a substantial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, such as insuf- ficient airflow across either coil or both coils.

REFRIGERANT CHARGE Ð The amount of refrigerant charge is listed on the unit nameplate and /or the physical data table. Refer to the Refrigeration Service Techniques Manual, Refrigerants Section.

NO CHARGE Ð Check for leak. Use standard evacuating tech- niques. After evacuating system, weigh in the specified amount of refrigerant (refer to system data plate).

LOW CHARGE COOLING Ð Use Cooling Charging Charts (Figs. 23-35). Vary refrigerant until the conditions of the chart are

met. Note that charging charts are different from type normally used. Charts are based on charging the units to correct superheat for the various operating conditions. Accurate pressure gage and temperature sensing devices are required. Connect the pressure gage to the service port on the suction line. Mount the temperature sensing device on the suction line and insulate it so that the outdoor ambient does not effect the reading. Indoor air CFM must be within the normal operating range of the unit.

TO USE COOLING CHARGING CHARTS Ð Take the outdoor ambient temperature and read the suction pressure gage. Refer to the chart to determine what the suction temperature should be. NOTE: If the problem causing the inaccurate readings is a refrigerant leak, refer to Check for Refrigerant Leaks section.

18

Page 18
Image 18
Carrier 50JS instruction manual BÐWet Coil Air Delivery, Unit 50JX 024-060Deduct 10% for