C99097
Fig. 36ÐRefrigerant Circuit
exists, be sure that all supply- and
METERING DEVICES Ð Refrigerant metering devices are fixed orifices and are located in the inlet header to the indoor and outdoor coils.
LIQUID LINE STRAINERS Ð The liquid line strainers (to pro- tect metering devices) are made of wire mesh and are located in the liquid lines on the inlet side of the metering devices.
SYSTEM INFORMATION
within a range of 15v to 30v and draws about 0.5 amps. If the blower runs continuously instead of cycling off when the fan switch is set on AUTO, the TDR is probably defective and must be replaced.
LOSS OF CHARGE SWITCH Ð The loss of charge switch is a protective device wired into control circuit (low voltage). It shuts off the compressor if abnormally low pressures are present in the refrigeration circuit.
NOTE: Because these switches are attached to refrigeration system under pressure, it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists. If switch must be removed, remove and recover all system charge so that pressure gages read 0 psi. Never open system without breaking vacuum with dry nitrogen.
CHECK DEFROST THERMOSTAT Ð There is a liquid header with a brass distributor and feeder tube going into outdoor coil. At the end of 1 of the feeder tubes, there is a
DEFROST THERMOSTATS Ð Defrost thermostat signals heat
FEEDER TUBE
STUB TUBE
DEFROST
THERMOSTAT
C99029
Fig. 37ÐDefrost Thermostat
pump that conditions are right for defrost or that conditions have changed to terminate defrost. It is a thermally actuated switch clamped to outdoor coil to sense its temperature. Normal tempera- ture range is closed at 30Ê +/- 3ÊF and open at 80Ê +/- 5ÊF.
NOTE: The defrost thermostat must be located on the liquid side of the outdoor coil on the bottom circuit and as close to the coil as possible.
23