Carrier 50JS ÐTypical Heat Pump Operation, Heating Mode, LCS - Loss of Charge Switch

Models: 50JS

1 28
Download 28 pages 58.47 Kb
Page 16
Image 16
LEGEND

OUTDOOR COIL

ACCUMULATOR

COMPRESSOR

Metering

Position

LEGEND

LCS – Loss of Charge Switch

LCS – Loss of Charge Switch Accurater® Metering DeviceArrow indicates direction of flowFig. 21ÐTypical Heat Pump Operation, Heating Mode Accurater® Metering Device

Arrow indicates direction of flow

Bypass Position

LCS

INDOOR COIL

C99027

1.Hot gas from compressor flows through the 4-way valve and is directed to the indoor coil. It is then condensed and subcooled through the coil circuits and then leaves the indoor coil by way of the ID Accurater in the bypass position to the liquid line.

2.The refrigerant then feeds the outdoor coil through the OD Accurater device in the metering position and distributes to each circuit.

3.Each circuit evaporates the refrigerant and the circuits are combined in the outdoor coil header.

4.The refrigerant then flows through the 4-way valve, accumulator, and back to the compressor.

Fig. 21ÐTypical Heat Pump Operation, Heating Mode

OUTDOOR COIL

ACCUMULATOR

COMPRESSOR

 

 

LEGEND

Bypass

 

Position

LCS – Loss of Charge Switch

Fig. 22ÐTypical Heat Pump Operation, Cooling Mode Accurater® Metering Device

Arrow indicates direction of flow

Metering

Position

LCS

INDOOR COIL

C99028

1.Hot gas from compressor flows through the 4-way valve and is directed to the outdoor coil. It is then condensed and subcooled through the coil circuits. Refrigerant leaves the outdoor coil by way of the OD Accurater in the bypass position to the liquid line.

2.The refrigerant then feeds the indoor coil through the ID Accurater device in the metering position and distributes to each circuit.

3.Each circuit evaporates the refrigerant and the circuits are combined in the indoor coil header.

4.The refrigerant then flows through the 4-way valve, accumulator, and back to the compressor.

Fig. 22ÐTypical Heat Pump Operation, Cooling Mode

16

Page 16
Image 16
Carrier 50JS instruction manual ÐTypical Heat Pump Operation, Heating Mode, ÐTypical Heat Pump Operation, Cooling Mode