Table 1 – Physical Data - Unit 50VT-A

50VT-- A

Table 1 – Physical Data - Unit 50VT-A

 

 

 

 

 

 

 

 

 

 

 

50VT-A24

50VT-A30

 

50VT-A36

 

50VT-A42

 

50VT-A48

50VT-A60

Unit Size

2

2.5

 

3

 

3.5

 

4

5

Shipping Weight (lb)

354

346

 

426

 

472

 

460

506

(kg)

161

157

 

193

 

214

 

209

230

Compressor Quantity

 

 

 

 

1

 

 

 

Type

 

 

 

 

Scroll

 

 

Refrigerant

 

 

 

 

R-410A

 

 

Refrigerant Quantity (lb)

11.1

10.3

 

9.9

 

11.3

 

12.5

15.2

Quantity (kg)

5.0

4.7

 

4.5

 

5.1

 

5.7

6.9

Refrigerant Metering Device

 

 

 

Indoor TXV, Outdoor

Dual Accuraters

 

 

 

Orifice OD (in)

0.032 (2)

0.037 (2)

 

0.038 (2)

 

0.040 (2)

 

0.040 (2)

0.049 (2)

(mm)

0.81 (2)

0.94 (2)

 

0.97 (2)

 

1.02 (2)

 

1.02 (2)

1.24 (2)

Outdoor Coil

 

 

 

 

 

 

 

 

 

Rows...Fins/in,

2...21

2...21

 

2...21

 

2...21

 

2...21

2...21

face area (sq. ft.)

13.6

13.6

 

13.6

 

17.5

 

17.5

23.3

Outdoor Fan

 

 

 

 

 

 

 

 

 

Nominal Airflow (cfm)

2500

2700

 

3100

 

3100

 

3100

3500

Diameter (in.)

24

24

 

26

 

26

 

26

26

Diameter (mm)

610

610

 

660

 

660

 

660

660

Motor hp (rpm)

1/10 (810)

1/5 (810)

 

1/5 (810)

 

1/5 (810)

 

1/5 (810)

1/4 (810)

Indoor Coil

 

 

 

 

 

 

 

 

 

Rows...Fins/in,

3...17

3...17

 

3...17

 

3...17

 

3...17

3...17

face area (sq. ft.)

3.7

3.7

 

4.7

 

4.7

 

5.6

5.6

Indoor Blower

 

 

 

 

 

 

 

 

 

Nominal Airflow (cfm)

800

1000

 

1200

 

1400

 

1600

1750

Size (in.)

10 x 10

10 x 10

 

11 x 10

 

11 x 10

 

11 x 10

11 x 10

Size (mm)

254 x 254

254 x 254

 

279 x 254

 

279 x 254

 

279 x 254

279 x 254

Motor hp (rpm)

1/2

1/2

 

3/4

 

3/4

 

1

1

High Pressure Switch (psig)

 

 

650 +/- 15

 

 

 

Cutout

 

 

 

 

 

Reset (Auto)

 

 

420 +/- 25

 

 

 

Loss-of-Charge/Low Pressure Switch (psig)

 

 

20 +/- 5

 

 

 

Cutout

 

 

 

 

 

Reset (Auto)

 

 

45 +/- 10

 

 

 

Return Air Filters

20x20x1

20x24x1

 

24x30x1

24x36x1

disposable (in)

 

(mm)

508x508x25

508x610x25

 

610x762x25

610x914x25

*Required filter sizes shown are based on the larger of the AHRI (Air Conditioning Heating and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute for throwaway type or 450 ft/minute for high ---capacity type. Air filter pressure drop for non ---standard filters must not exceed 0.08 IN. W.C.

{If using accessory filter rack refer to the filter rack installation instructions for correct filter size and quantity. } For 460 volt units, add 14 lb (6.4 kg) to the weight.

Table 2 – Minimum Airflow for Reliable Electric Heater Operation (CFM)

SIZE

50VT-A24

50VT-A30
50VT-A36
50VT-A42
50VT-A48
50VT-A60
AIRFLOW (CFM)

800

1025

1250

1400

1710

1800

TOP COVER SIZE
INDOOR

50VT-A2450VT-A3050VT-A3650VT-A4250VT-A48 THERMOSTAT

RETURN

AIR 50VT-A60

FROM

POWER

SOURCE

DISCONNECT

PER NEC

POWER ENTRY

CONTROL ENTRY

A09098

Fig. 11 - Typical Installation