Table 1 – Physical Data - Unit 50VT-A
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
Unit Size | 2 | 2.5 |
| 3 |
| 3.5 |
| 4 | 5 |
Shipping Weight (lb) | 354 | 346 |
| 426 |
| 472 |
| 460 | 506 |
(kg) | 161 | 157 |
| 193 |
| 214 |
| 209 | 230 |
Compressor Quantity |
|
|
|
| 1 |
|
|
| |
Type |
|
|
|
| Scroll |
|
| ||
Refrigerant |
|
|
|
|
|
| |||
Refrigerant Quantity (lb) | 11.1 | 10.3 |
| 9.9 |
| 11.3 |
| 12.5 | 15.2 |
Quantity (kg) | 5.0 | 4.7 |
| 4.5 |
| 5.1 |
| 5.7 | 6.9 |
Refrigerant Metering Device |
|
|
| Indoor TXV, Outdoor | Dual Accuraters |
|
|
| |
Orifice OD (in) | 0.032 (2) | 0.037 (2) |
| 0.038 (2) |
| 0.040 (2) |
| 0.040 (2) | 0.049 (2) |
(mm) | 0.81 (2) | 0.94 (2) |
| 0.97 (2) |
| 1.02 (2) |
| 1.02 (2) | 1.24 (2) |
Outdoor Coil |
|
|
|
|
|
|
|
|
|
Rows...Fins/in, | 2...21 | 2...21 |
| 2...21 |
| 2...21 |
| 2...21 | 2...21 |
face area (sq. ft.) | 13.6 | 13.6 |
| 13.6 |
| 17.5 |
| 17.5 | 23.3 |
Outdoor Fan |
|
|
|
|
|
|
|
|
|
Nominal Airflow (cfm) | 2500 | 2700 |
| 3100 |
| 3100 |
| 3100 | 3500 |
Diameter (in.) | 24 | 24 |
| 26 |
| 26 |
| 26 | 26 |
Diameter (mm) | 610 | 610 |
| 660 |
| 660 |
| 660 | 660 |
Motor hp (rpm) | 1/10 (810) | 1/5 (810) |
| 1/5 (810) |
| 1/5 (810) |
| 1/5 (810) | 1/4 (810) |
Indoor Coil |
|
|
|
|
|
|
|
|
|
Rows...Fins/in, | 3...17 | 3...17 |
| 3...17 |
| 3...17 |
| 3...17 | 3...17 |
face area (sq. ft.) | 3.7 | 3.7 |
| 4.7 |
| 4.7 |
| 5.6 | 5.6 |
Indoor Blower |
|
|
|
|
|
|
|
|
|
Nominal Airflow (cfm) | 800 | 1000 |
| 1200 |
| 1400 |
| 1600 | 1750 |
Size (in.) | 10 x 10 | 10 x 10 |
| 11 x 10 |
| 11 x 10 |
| 11 x 10 | 11 x 10 |
Size (mm) | 254 x 254 | 254 x 254 |
| 279 x 254 |
| 279 x 254 |
| 279 x 254 | 279 x 254 |
Motor hp (rpm) | 1/2 | 1/2 |
| 3/4 |
| 3/4 |
| 1 | 1 |
High Pressure Switch (psig) |
|
| 650 +/- 15 |
|
|
| |||
Cutout |
|
|
|
|
| ||||
Reset (Auto) |
|
| 420 +/- 25 |
|
|
| |||
|
| 20 +/- 5 |
|
|
| ||||
Cutout |
|
|
|
|
| ||||
Reset (Auto) |
|
| 45 +/- 10 |
|
|
| |||
Return Air Filters | 20x20x1 | 20x24x1 |
| 24x30x1 | 24x36x1 | ||||
disposable (in) |
| ||||||||
(mm) | 508x508x25 | 508x610x25 |
| 610x762x25 | 610x914x25 |
*Required filter sizes shown are based on the larger of the AHRI (Air Conditioning Heating and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute for throwaway type or 450 ft/minute for high
{If using accessory filter rack refer to the filter rack installation instructions for correct filter size and quantity. } For 460 volt units, add 14 lb (6.4 kg) to the weight.
Table 2 – Minimum Airflow for Reliable Electric Heater Operation (CFM)
SIZE |
|
|
|
|
|
|
AIRFLOW (CFM) | 800 | 1025 | 1250 | 1400 | 1710 | 1800 |
TOP COVER
INDOOR
THERMOSTAT
RETURN
AIR
FROM
POWER
SOURCE
DISCONNECT
PER NEC
POWER ENTRY
CONTROL ENTRY
A09098
Fig. 11 - Typical Installation
10