![Standard Connections](/images/new-backgrounds/33655/3365517x1.webp)
HIGH VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)
TWO POWER | EQUIP GR |
LEADS |
CONTROL BOX
POWER
SUPPLY
control voltage wires), use no. 16 AWG
Standard Connections
Locate the eight (nine on
WIRING LABEL
SPLICE BOX
WHT(W1) | W1 |
| |
VIO (W2) | W2 |
| |
YEL(Y) | Y |
| |
GRN(G) | G |
| |
RED(R) | R |
| |
BRN(C) | C |
| |
ORN(O) | O |
| |
BLU(DH) | DH |
| |
GRA(Y2) | |
| |
| Only |
THERMOSTAT (TYPICAL)
operation of unit. A gray wire is standard on
If an accessory electric heater is installed, low voltage leads from heater must be connected to factory supplied control leads from Indoor Fan Board P4 connector.
NOTE: If the unit 24V wires do not have a matching receptacle, cut the 24V wires from the electric heater plug, strip the ends, and wire nut together to match the schematic connections. If the electric heater 24V wires do not have a matching plug, cut the 24V wires from the unit receptacle, strip the ends, and wire nut together to match the schematic connections.
A09071
Fig. 10 - High- and Control-Voltage Connections
Single phase units:
1.Run the
2.Connect ground lead to chassis ground connection.
3.Locate the black and yellow wires connected to the line side of the contactor.
4.Connect field L1 to black wire on connection 11 of the compressor contactor.
5.Connect field wire L2 to yellow wire on connection 23 of the compressor contactor.
1.Run the
2.Connect ground lead to chassis ground connection.
3.Locate the black and yellow wires connected to the line side of the contactor.
4.Connect field L1 to black wire on connection 11 of the compressor contactor.
5.Connect field wire L3 to yellow wire on connection 13 of the compressor contactor.
6.Connect field wire L2 to blue wire from compressor.
Special Procedures for 208-V Operation
!WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system. Tag the disconnect switch with a suitable warning label. With disconnect switch open, move black wire from transformer (3/16 in.) terminal marked 230 to terminal marked 208. This retaps transformer to primary voltage of 208 vac.
Control Voltage Connections
NOTE: Do not use any type of
Use no. 18 American Wire Gage (AWG)
Factory wires are provided for electric heat staging W1 and W2 (W2 and W3 on IFB). If room thermostat has only one stage of supplemental heat, connect white and violet wires shown in Fig. 10 to second stage heat field wire.
Some electric heaters have four control wires (plus common wire). Consult unit wiring diagram and electric heater wiring diagram for additional details.
Transformer Protection
The transformer is of the
Accessory Electric Heaters Installation
Electric heaters may be installed with the
Sequence of Operation
a. CONTINUOUS FAN
(1.) Thermostat closes circuit R to G energizing the blower motor for continuous fan.
b. COOLING MODE
(1.) If indoor temperature is above temperature set point, thermostat closes circuits R to G, R to Y and
Rto
c.ELECTRIC HEATING MODE
(1.) Thermostat closes circuit R to W/W1, or W2 and R to G. There are no on or off delays.
d.HEAT PUMP HEATING MODE
(1.) Thermostat closes circuits R to G and R to Y. The compressor, indoor and outdoor fans are energized.
e.HEAT PUMP HEATING WITH AUXILIARY ELECTRIC HEAT
(1.) Thermostat closes circuits R to G, R to Y and R to W/W1 or W2. The compressor, indoor and outdoor fans are energized, as well as the electric heat relays.
f.DEFROST MODE
The defrost mode is automatically energized by the defrost board during heating mode. The defrost board energizes “O” (reversing valve) and “W2” (electric heat). It also
9