AIRFLOW
12″
4″ D
FILTER RETAINERS
Fig. 11ÐHorizontal Filter Arrangement
Table 4ÐFilter Retainer (In.)
FURNACE CASING | FILTER SIZE AND | D | |
WIDTH | QUANTITY | ||
| |||
(2) 14 X 20 X 1 | |||
(2) 14 X 20 X 1 | |||
21 | (2) 16 X 20 X 1 | ||
(2) 16 X 20 X 1 |
AIRFLOW
INSTALLATION
POSITION
OF FILTERS
PLENUM
ACCESS DOOR
A88486
Fig. 12ÐDownflow Filter Arrangement
Use the proper length of pipes to avoid stress on the gas control manifold. Failure to follow this warning could result in a gas leak, causing fire, explosion, personal injury, or death.
Table 5ÐMaximum Capacity of Gas Pipe *
NOMINAL IRON | INTERNAL | LENGTH OF PIPE (FT) |
| ||||
PIPE SIZE | DIAMETER |
|
|
|
|
|
|
10 | 20 | 30 | 40 |
| 50 | ||
(IN.) | (IN.) |
| |||||
1/2 | 0.622 | 175 | 120 | 97 | 82 |
| 73 |
3/4 | 0.824 | 360 | 250 | 200 | 170 |
| 151 |
1 | 1.049 | 680 | 465 | 375 | 320 |
| 285 |
1.380 | 1400 | 950 | 770 | 660 |
| 580 | |
1.610 | 2100 | 1460 | 1180 | 990 |
| 900 |
*Cubic ft of gas per hr for gas pressures of 0.5 psig
Connect the gas pipe to the furnace using a backup wrench to avoid damaging gas controls.
Never purge a line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition to check for gas leakage. Use a
Joint compounds (pipe dope) should be applied sparingly and only to the male threads of the joints. This pipe dope must be resistant to the action of propane gas.
An accessible manual shutoff valve MUST be installed upstream of the furnace gas controls and within 72 in. of the furnace. A
Install a sediment trap in the riser leading to the furnace. The trap can be installed by connecting a tee to the riser leading from the furnace. Connect a capped nipple into the lower end of the tee. The capped nipple should extend below the level of the gas controls. (See Fig. 13.)
Piping should be pressure tested in accordance with local and national plumbing and gas codes before the furnace has been attached. If the pressure exceeds 0.5 psig
0.5psig
After all connections have been made, purge the lines and check for gas leakage with regulated gas supply pressure.
Step 10ÐElectrical Connections
Refer to the unit rating plate or Table 6 for equipment electrical requirements. The control system requires an earth ground for proper operation.
Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire.
Make all electrical connections in accordance with the current edition of the National Electrical Code (NEC) ANSI/NFPA
10