Table 6ÐElectrical Data
| VOLTSÐ | OPERATING VOLTAGE RANGE | MAXIMUM | MINIMUM | MAXIMUM WIRE | MAXIMUM | ||
UNIT SIZE | HERTZÐ |
|
| FUSE OR CKT BKR | ||||
Maximum* | Minimum* | UNIT AMPS | WIRE GAGE | LENGTH FT³ | ||||
| PHASE | AMPS² | ||||||
|
|
|
| |||||
115Ð60Ð1 | 127 | 104 | 6.6 | 14 | 42 | 15 | ||
115Ð60Ð1 | 127 | 104 | 8.1 | 14 | 34 | 15 | ||
115Ð60Ð1 | 127 | 104 | 6.7 | 14 | 42 | 15 | ||
115Ð60Ð1 | 127 | 104 | 8.4 | 14 | 33 | 15 | ||
115Ð60Ð1 | 127 | 104 | 9.2 | 14 | 30 | 15 | ||
115Ð60Ð1 | 127 | 104 | 10.2 | 14 | 28 | 15 | ||
115Ð60Ð1 | 127 | 104 | 10.1 | 14 | 28 | 15 | ||
115Ð60Ð1 | 127 | 104 | 13.3 | 12 | 33 | 20 | ||
115Ð60Ð1 | 127 | 104 | 15.2 | 12 | 29 | 20 | ||
115Ð60Ð1 | 127 | 104 | 14.3 | 12 | 31 | 20 | ||
|
|
|
|
|
|
|
|
*Permissible limits of the voltage range at which the unit will operate satisfactorily. ²
³ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
GAS
SUPPLY
MANUAL
SHUTOFF VALVE (REQUIRED)
SEDIMENT
TRAP
UNION
A89414
Fig. 13ÐTypical Gas Pipe Arrangement
Canadian installations, all electrical connections must be made in accordance with Canadian Electrical Code CSA C22.1, or authori- ties having jurisdiction.
NOTE: Proper polarity must be maintained for
The cabinet MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA
Make field
The
ACCESSORIES
1.Electronic Air Cleaner (EAC)
Two spring clamp terminals (for 12 gage maximum, solid or stranded wire), marked
2.Humidifier (HUM)
Screw terminals (HUM and
→Do not connect furnace control HUM terminal to HUM (humidifier) terminal on Thermidistat™, Zone Controller, or similar device. See Thermidistat, Zone Controller, thermostat, or controller manufacturer's instructions for proper connec- tion. A failure to follow this warning could result in fire.
NOTE: A
Step 11ÐVenting
→Refer to the national or local installation code such as NFGC in the United States, or the NSCNGPIC in Canada for proper vent sizing and installation requirements. Use the enclosed Installation In- structions
→After fully assembling the vent connector to the furnace flue collar, securely fasten the vent connector to the collar with two field- supplied,
The horizontal portion of the venting system shall maintain a minimum of