→Table 7ÐModel 58ZAV Orifice Size² and Manifold Pressure for Correct Input (Continued)
(Tabulated Data Based on 23,000 BTUH Per Burner, Derated 4 percent per 1000 Ft Above Sea Level)*
| ALTITUDE | AVG GAS |
|
|
|
|
| SPECIFIC GRAVITY OF NATURAL GAS |
|
|
| |||||||
| HEAT VALUE |
| 0.58 |
| 0.60 |
| 0.62 |
| 0.64 |
| 0.66 | |||||||
|
| RANGE |
|
|
|
|
| |||||||||||
|
| (FT) | AT ALTITUDE | Orifice |
| Manifold | Orifice |
| Manifold | Orifice |
| Manifold | Orifice |
| Manifold | Orifice |
| Manifold |
|
| (BTU/CU FT) |
|
|
|
|
| |||||||||||
|
|
| No. |
| Pressure | No. |
| Pressure | No. |
| Pressure | No. |
| Pressure | No. |
| Pressure | |
|
|
| 575 | 43 |
| 3.0 | 43 |
| 3.1 | 43 |
| 3.2 | 43 |
| 3.3 | 43 |
| 3.4 |
|
|
| 600 | 43 |
| 2.7 | 43 |
| 2.8 | 43 |
| 2.9 | 43 |
| 3.0 | 43 |
| 3.1 |
Only |
| 9001 | 625 | 43 |
| 2.5 | 43 |
| 2.6 | 43 |
| 2.7 | 43 |
| 2.8 | 43 |
| 2.8 |
|
| 650 | 43 |
| 2.3 | 43 |
| 2.4 | 43 |
| 2.5 | 43 |
| 2.6 | 43 |
| 2.6 | |
|
|
|
|
|
|
|
| |||||||||||
U.S.A. |
| to | 675 | 43 |
| 2.1 | 43 |
| 2.2 | 43 |
| 2.3 | 43 |
| 2.4 | 43 |
| 2.4 |
|
| 700 | 48 |
| 3.8 | 43 |
| 2.1 | 43 |
| 2.1 | 43 |
| 2.2 | 43 |
| 2.3 | |
|
|
|
|
|
|
|
| |||||||||||
|
| 10,000 | 725 | 48 |
| 3.5 | 48 |
| 3.6 | 48 |
| 3.7 | 43 |
| 2.1 | 43 |
| 2.1 |
|
|
| 750 | 49 |
| 3.8 | 48 |
| 3.4 | 48 |
| 3.5 | 48 |
| 3.6 | 48 |
| 3.7 |
|
|
| 775 | 49 |
| 3.6 | 49 |
| 3.7 | 49 |
| 3.8 | 48 |
| 3.4 | 48 |
| 3.5 |
*For size
² Orifice sizes shown in BOLD are factory installed.
NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A
Table 8ÐAltitude Derate Multiplier for U.S.A.
ALTITUDE | % OF | DERATE MULTIPLIER |
(FT) | DERATE | FACTOR FOR U.S.A* |
|
|
|
0Ð2000 | 0 | 1.00 |
|
|
|
2001Ð3000 | 8Ð12 | 0.90 |
|
|
|
3001Ð4000 | 12Ð16 | 0.86 |
4001Ð5000 | 16Ð20 | 0.82 |
|
|
|
5001Ð6000 | 20Ð24 | 0.78 |
|
|
|
6001Ð7000 | 24Ð28 | 0.74 |
7001Ð8000 | 28Ð32 | 0.70 |
|
|
|
8001Ð9000 | 32Ð36 | 0.66 |
|
|
|
9001Ð10,000 | 36Ð40 | 0.62 |
|
|
|
* Derate multiplier factor is based on midpoint altitude for altitude range.
BURNER
ORIFICE
A93059
DO NOT redrill orifices. Improper drilling (burrs,
(3.) After correct manifold pressure is obtained, replace gas valve regulator adjustment screw cap and verify adjusted gas input rate using method outlined in item c.
(4.) Burner flame should be clear blue, almost transparent. (See Fig. 19.)
c. Verify natural gas input rate by clocking gas meter.
NOTE:
United States
At installation altitudes above 2000 ft, this furnace has been approved for a 4 percent derate for each 1000 ft above sea level. See Table 8 for derate multiplier factor.
EXAMPLE:
92,000 Btuh input furnace installed at 4300 ft.
Furnace Input |
| Derate |
| Furnace Input Rate |
Rate at | X | Multiplier | = | at Installation |
Sea Level |
| Factor |
| Altitude |
92,000 |
| 0.82 |
| 75,440 |
Canada
At installation altitudes from 2000 to 4500 ft, this furnace must be derated 10 percent by an authorized Gas Conversion Station. To determine correct input rate for altitude, see example above and use 0.90 as derate multiplier factor.
a.Turn off all other gas appliances and pilots.
b.Start furnace and let operate for 3 minutes.
c.Measure time (in sec) for gas meter test dial to complete 1 revolution.
d.Refer to Table 9 for cu ft of gas per hr.
e.Multiply gas rate (cu ft/hr) X heating value (Btu/cu ft) using natural gas heating value from local gas utility/supplier.
18