Table 7ÐModel 58ZAV Orifice Size² and Manifold Pressure for Correct Input

(Tabulated Data Based on 23,000 BTUH Per Burner, Derated 4 Percent per 1000 Ft Above Sea Level)*

 

ALTITUDE

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

HEAT VALUE

 

0.58

 

0.60

 

0.62

 

0.64

 

0.66

 

 

RANGE

 

 

 

 

 

 

 

(FT)

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

(BTU/CU FT)

 

 

 

 

 

 

 

 

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

 

 

 

850

41

 

3.6

41

 

3.7

41

 

3.8

40

 

3.6

40

 

3.8

 

 

 

875

42

 

3.8

41

 

3.5

41

 

3.6

41

 

3.7

41

 

3.8

Canada

 

 

900

42

 

3.5

42

 

3.7

42

 

3.8

41

 

3.5

41

 

3.6

 

0

925

42

 

3.4

42

 

3.5

42

 

3.6

42

 

3.7

42

 

3.8

 

 

950

42

 

3.2

42

 

3.3

42

 

3.4

42

 

3.5

42

 

3.6

and

 

to

975

43

 

3.7

43

 

3.8

42

 

3.2

42

 

3.3

42

 

3.4

 

 

1000

43

 

3.5

43

 

3.6

43

 

3.7

42

 

3.2

42

 

3.3

U.S.A.

 

 

 

 

 

 

 

 

2000

1025

43

 

3.3

43

 

3.4

43

 

3.6

43

 

3.7

43

 

3.8

 

 

1050

43

 

3.2

43

 

3.3

43

 

3.4

43

 

3.5

43

 

3.6

 

 

 

 

 

 

 

 

 

 

 

1075

44

 

3.5

44

 

3.6

43

 

3.2

43

 

3.3

43

 

3.4

 

 

 

1100

44

 

3.3

44

 

3.4

44

 

3.5

43

 

3.2

43

 

3.3

 

ALTITUDE

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

HEAT VALUE

 

0.58

 

0.60

 

0.62

 

0.64

 

0.66

 

 

RANGE

 

 

 

 

 

 

 

(FT)

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

(BTU/CU FT)

 

 

 

 

 

 

 

 

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U.S.A

775

42

 

3.7

42

 

3.8

41

 

3.5

41

 

3.6

41

 

3.8

 

 

Altitudes

800

42

 

3.4

42

 

3.6

42

 

3.7

42

 

3.8

41

 

3.5

Canada

 

2001

825

42

 

3.2

42

 

3.3

42

 

3.5

42

 

3.6

42

 

3.7

 

to

850

43

 

3.7

43

 

3.8

42

 

3.3

42

 

3.4

42

 

3.5

 

3000

875

43

 

3.5

43

 

3.6

43

 

3.7

42

 

3.2

42

 

3.3

and

 

or

900

43

 

3.3

43

 

3.4

43

 

3.5

43

 

3.7

43

 

3.8

 

Canada

925

43

 

3.1

43

 

3.2

43

 

3.4

43

 

3.5

43

 

3.6

U.S.A.

 

 

 

 

 

 

 

Altitudes

950

43

 

3.0

43

 

3.1

43

 

3.2

43

 

3.3

43

 

3.4

 

2000

975

43

 

2.8

43

 

2.9

43

 

3.0

43

 

3.1

43

 

3.2

 

 

 

 

 

 

 

 

 

to

1000

43

 

2.7

43

 

2.8

43

 

2.9

43

 

3.0

43

 

3.1

 

 

4500

1025

43

 

2.6

43

 

2.6

43

 

2.7

43

 

2.8

43

 

2.9

 

ALTITUDE

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

HEAT VALUE

 

0.58

 

0.60

 

0.62

 

0.64

 

0.66

 

 

RANGE

 

 

 

 

 

 

 

(FT)

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

(BTU/CU FT)

 

 

 

 

 

 

 

 

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

750

42

 

3.4

42

 

3.6

42

 

3.7

42

 

3.8

41

 

3.5

 

 

 

775

42

 

3.2

42

 

3.3

42

 

3.5

42

 

3.6

42

 

3.7

 

 

 

800

43

 

3.7

43

 

3.8

42

 

3.2

42

 

3.3

42

 

3.4

Only

 

3001

825

43

 

3.5

43

 

3.6

43

 

3.7

43

 

3.8

42

 

3.2

 

 

850

43

 

3.3

43

 

3.4

43

 

3.5

43

 

3.6

43

 

3.7

 

to

875

43

 

3.1

43

 

3.2

43

 

3.3

43

 

3.4

43

 

3.5

U.S.A.

 

 

 

 

 

 

 

 

900

43

 

2.9

43

 

3.0

43

 

3.1

43

 

3.2

43

 

3.3

 

4000

925

43

 

2.8

43

 

2.9

43

 

3.0

43

 

3.0

43

 

3.1

 

 

 

 

 

 

 

 

 

 

950

43

 

2.6

43

 

2.7

43

 

2.8

43

 

2.9

43

 

3.0

 

 

 

975

43

 

2.5

43

 

2.6

43

 

2.7

43

 

2.7

43

 

2.8

 

 

 

1000

43

 

2.4

43

 

2.4

43

 

2.5

43

 

2.6

43

 

2.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALTITUDE

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

HEAT VALUE

 

0.58

 

0.60

 

0.62

 

0.64

 

0.66

 

 

RANGE

 

 

 

 

 

 

 

(FT)

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

(BTU/CU FT)

 

 

 

 

 

 

 

 

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

725

42

 

3.2

42

 

3.3

42

 

3.5

42

 

3.6

42

 

3.7

 

 

 

750

43

 

3.7

43

 

3.8

42

 

3.2

42

 

3.3

42

 

3.4

Only

 

 

775

43

 

3.4

43

 

3.6

43

 

3.7

43

 

3.8

42

 

3.2

 

4001

800

43

 

3.2

43

 

3.3

43

 

3.5

43

 

3.6

43

 

3.7

 

 

825

43

 

3.0

43

 

3.1

43

 

3.2

43

 

3.4

43

 

3.5

U.S.A.

 

 

 

 

 

 

 

 

to

850

43

 

2.9

43

 

3.0

43

 

3.1

43

 

3.2

43

 

3.3

 

 

875

43

 

2.7

43

 

2.8

43

 

2.9

43

 

3.0

43

 

3.1

 

 

5000

900

43

 

2.6

43

 

2.6

43

 

2.7

43

 

2.8

43

 

2.9

 

 

 

925

43

 

2.4

43

 

2.5

43

 

2.6

43

 

2.7

43

 

2.8

 

 

 

950

43

 

2.3

43

 

2.4

43

 

2.5

43

 

2.5

43

 

2.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*For size 135-20 only, input is 22,500 Btuh per burner. Deduct 0.1-in. wc from manifold pressure shown in table. Change orifice size if manifold pressure falls below 3.2-in. wc on altitudes up to 2000 ft, otherwise change orifice size if manifold pressure falls below 2.0-in. wc.

² Orifices sizes shown in BOLD are factory installed.

16

Page 16
Image 16
Carrier 58ZAV operating instructions Altitude