Electrical Data

 

 

 

 

 

 

 

 

 

 

 

 

GT-PX (50YDS) Electrical Data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

HWG

External

Total

Min

Max

 

Min

Max

Model

 

 

 

 

 

Pump

Pump

Unit

Circuit

Fuse/

 

Wire Ft.

RLA

 

LRA

 

Qty

 

AWG

 

 

 

FLA

FLA

FLA

Amps

HACR

 

(m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

026

10.3

 

52

 

1

0.4

4.0

14.7

17.2

25

 

10

110 (33.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

038

16.7

 

82

 

1

0.4

4.0

21.0

25.2

40

 

8

120 (36.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

049

21.2

 

96

 

1

0.4

4.0

25.5

30.8

50

 

6

160 (48.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

064

25.6

 

118

 

1

0.4

4.0

30.0

36.4

60

 

6

135 (41.0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated Voltage of 208/230/60/1

Min/Max Voltage of 197/254

HACR circuit breaker in USA only

All fuses Class RK-5

Wire length based on one way measurement with 2% voltage drop

Wire size based on 60°C copper conductor

GT-GS (50YCS) Electrical Data

 

 

Compressor

 

HWG

External

Total

Min

Max

Min

Max

Model

 

 

 

 

 

Pump

Pump

Unit

Circuit

Fuse/

Wire Ft

RLA

 

LRA

 

Qty

AWG

 

 

 

FLA

FLA

FLA

Amps

HACR

(m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

018

9.0

 

42.0

 

1

0.40

4.0

13.4

15.7

20

12

80 (24.4)

 

 

 

 

 

 

 

 

 

 

 

 

 

024

10.3

 

56.0

 

1

0.40

4.0

14.6

17.2

25

10

110 (33.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

030

12.2

 

67.0

 

1

0.40

4.0

16.5

19.6

30

10

100 (30.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

036

13.5

 

73.0

 

1

0.40

4.0

17.8

21.2

30

10

90 (27.4)

 

 

 

 

 

 

 

 

 

 

 

 

 

042

16.5

 

95.0

 

1

0.40

4.0

20.9

25.0

40

8

120 (36.6)

 

 

 

 

 

 

 

 

 

 

 

 

 

048

18.3

 

109.0

 

1

0.40

4.0

22.7

27.3

45

6

180 (54.9)

 

 

 

 

 

 

 

 

 

 

 

 

 

060

25.0

 

169.0

 

1

0.40

4.0

29.3

35.6

60

6

140 (42.7)

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated Voltage of 208/230/60/1

Min/Max Voltage of 197/254

HACR circuit breaker in USA only

All fuses Class RK-5

Wire length based on one way measurement with 2% voltage drop

Wire size based on 60°C copper conductor

GT-S (38WQS) Electrical Data

 

 

Compressor

 

HWG

Ext Loop

Total

Min

Max

Min

Max

Model

 

 

 

 

Crank-

Pump

Pump

Unit

Circuit

Fuse/

Wire Ft

RLA

LRA

Qty

 

AWG

 

 

FLA

FLA

FLA

Amps

HACR

(m)

 

 

case

 

 

 

 

 

 

 

 

 

 

 

 

 

018

7.1

38.0

1

 

N/A

0.40

4.0

11.2

12.9

20

12

90 (27.4)

 

 

 

 

 

 

 

 

 

 

 

 

 

024

10.3

56.0

1

 

0.17

0.40

4.0

14.4

17.0

25

10

120 (36.6)

 

 

 

 

 

 

 

 

 

 

 

 

 

030

12.2

67.0

1

 

0.17

0.40

4.0

16.4

19.4

30

10

100 (30.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

036

13.5

73.0

1

 

0.17

0.40

4.0

17.6

21.0

30

10

90 (27.4)

 

 

 

 

 

 

 

 

 

 

 

 

 

042

16.5

95.0

1

 

0.17

0.40

4.0

20.7

24.8

40

8

120 (36.6)

 

 

 

 

 

 

 

 

 

 

 

 

 

048

18.3

109.0

1

 

0.17

0.40

4.0

22.5

27.1

45

8

110 (33.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

060

28.9

169.0

1

 

0.29

0.40

4.0

33.1

40.4

60

6

120 (36.6)

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated Voltage of 208/230/60/1

Min/Max Voltage of 197/254

HACR circuit breaker in USA only

All fuses Class RK-5

Wire length based on one way measurement with 2% voltage drop

Wire size based on 60°C copper conductor

38

Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05

Page 40
Image 40
Carrier specifications GT-PX 50YDS Electrical Data, GT-GS 50YCS Electrical Data, GT-S 38WQS Electrical Data