GT-PX

 

 

 

 

 

 

 

 

 

 

 

Performance Correction Factors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow Correction Factors

 

 

 

 

 

 

 

TT Full Load Air Flow Corrections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

Cooling

 

 

 

Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM Per

% of

 

 

Total Cap

Sens Cap

Power

Heat of Rej

 

Htg Cap

Power

Heat of Ext

 

 

 

Ton of Clg

Nominal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

240

60

0.925

0.788

0.913

0.922

0.946

1.153

0.896

 

 

 

 

275

69

 

 

0.946

0.829

0.926

0.942

 

0.959

1.107

0.924

 

 

 

 

300

75

 

 

0.960

0.861

0.937

0.955

 

0.969

1.078

0.942

 

 

 

 

325

81

 

 

0.972

0.895

0.950

0.968

 

0.977

1.053

0.959

 

 

 

 

350

88

 

 

0.983

0.930

0.965

0.979

 

0.985

1.032

0.974

 

 

 

 

375

94

 

 

0.992

0.965

0.982

0.990

 

0.993

1.014

0.988

 

 

 

 

400

100

 

 

1.000

1.000

1.000

1.000

 

1.000

1.000

1.000

 

 

 

 

425

106

 

 

1.007

1.033

1.020

1.009

 

1.006

0.989

1.011

 

 

 

 

450

113

 

 

1.012

1.064

1.042

1.018

 

1.012

0.982

1.019

 

 

 

 

475

119

 

 

1.016

1.092

1.066

1.025

 

1.018

0.979

1.027

 

 

 

 

500

125

 

 

1.018

1.116

1.091

1.032

 

1.022

0.977

1.033

 

 

520

130

1.019

1.132

1.112

1.037

1.026

0.975

1.038

 

 

TT Part Load Air Flow Corrections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

Cooling

 

 

 

Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM Per

% of

 

 

Total Cap

Sens Cap

Power

Heat of Rej

 

Htg Cap

Power

Heat of Ext

 

 

 

Ton of Clg

Nominal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

240

60

0.920

0.781

0.959

0.927

0.946

1.241

0.881

 

 

 

275

69

 

0.942

0.832

0.964

0.946

0.960

1.163

0.915

 

 

 

300

75

 

0.956

0.867

0.969

0.959

0.969

1.115

0.937

 

 

 

325

81

 

0.969

0.901

0.975

0.970

0.978

1.076

0.956

 

 

 

350

88

 

0.981

0.934

0.982

0.981

0.986

1.043

0.973

 

 

 

375

94

 

0.991

0.967

0.990

0.991

0.993

1.018

0.988

 

 

 

400

100

 

1.000

1.000

1.000

1.000

1.000

1.000

1.000

 

 

 

425

106

 

1.007

1.033

1.011

1.008

1.006

0.990

1.010

 

 

 

450

113

 

1.013

1.065

1.023

1.015

1.012

0.986

1.017

 

 

 

475

119

 

1.018

1.098

1.036

1.021

1.017

0.983

1.024

 

 

 

500

125

 

1.021

1.131

1.051

1.026

1.021

0.981

1.030

 

 

520

130

1.023

1.159

1.063

1.030

1.024

0.979

1.034

 

 

Entering Air Correction Factors

TT Full Load Entering Air Corrections

Full Load Heating Corrections

Ent Air DB

Htg Cap

Power

Heat of

°F

Ext

 

 

 

 

 

 

40

1.052

0.779

1.120

45

1.043

0.808

1.102

50

1.035

0.841

1.084

55

1.027

0.877

1.065

60

1.019

0.915

1.045

65

1.010

0.957

1.023

68

1.004

0.982

1.010

70

1.000

1.000

1.000

75

0.989

1.045

0.974

80

0.976

1.093

0.946

 

 

 

 

 

 

Full Load Cooling Corrections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sens Clg Cap Multipliers- Entering DB °F

 

 

 

 

Ent Air

Total Clg

 

 

 

 

 

 

 

 

 

 

 

Power

Heat of

 

 

 

 

 

 

 

 

 

 

 

WB °F

Cap

60

65

70

75

80

80.6

85

90

95

100

 

Rej

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45

0.832

1.346

1.461

1.603

*

*

*

*

*

*

*

0.946

0.853

50

0.850

1.004

1.174

1.357

*

*

*

*

*

*

*

0.953

0.870

55

0.880

0.694

0.902

1.115

1.331

*

*

*

*

*

*

0.964

0.896

60

0.922

 

0.646

0.875

1.103

1.329

1.356

*

*

*

*

0.977

0.932

65

0.975

 

 

0.639

0.869

1.096

1.123

1.320

*

*

*

0.993

0.979

66.2

0.990

 

 

0.582

0.812

1.039

1.066

1.262

1.482

*

*

0.997

0.991

67

1.000

 

 

0.545

 

0.774

1.000

1.027

1.223

1.444

*

*

1.000

1.000

70

1.040

 

 

 

0.630

0.853

0.880

1.075

1.297

1.517

*

1.011

1.035

75

1.117

 

 

 

 

 

0.601

0.627

0.821

1.046

1.275

1.510

1.033

1.101

* Sensible capacity equals total capacity (no latent capacity) at conditions shown as "*"

 

 

 

 

Rev.: 03/29/04

ARI/ISO/ASHRAE 13256-1 uses entering air conditions of Clg- 80.6°F DB/66.2°F WB and Htg- 68°F DB/59°F WB

 

 

 

TT Part Load Entering Air Corrections

Part Load Heating Corrections

Ent Air DB

Htg Cap

Power

Heat of

°F

Ext

 

 

 

 

 

 

40

1.084

0.732

1.161

45

1.073

0.764

1.140

50

1.060

0.802

1.117

55

1.046

0.846

1.090

60

1.031

0.893

1.061

65

1.016

0.945

1.031

68

1.006

0.978

1.013

70

1.000

1.000

1.000

75

0.984

1.058

0.968

80

0.968

1.117

0.936

 

 

 

 

 

 

Part Load Cooling Corrections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sens Clg Cap Multipliers- Entering DB °F

 

 

 

 

Ent Air

Total Clg

 

 

 

 

 

 

 

 

 

 

 

Power

Heat of

 

 

 

 

 

 

 

 

 

 

 

WB °F

Cap

60

65

70

75

80

80.6

85

90

95

100

 

Rej

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45

0.876

1.286

1.302

1.389

*

*

*

*

*

*

*

0.981

0.895

50

0.883

1.002

1.099

1.241

*

*

*

*

*

*

*

0.985

0.901

55

0.903

0.706

0.871

1.060

1.271

*

*

*

*

*

*

0.989

0.918

60

0.935

 

0.617

0.844

1.079

1.319

1.349

*

*

*

*

0.993

0.945

65

0.979

 

 

0.595

0.849

1.098

1.128

1.342

*

*

*

0.998

0.982

66.2

0.991

 

 

0.531

0.789

1.040

1.070

1.284

1.522

*

*

0.999

0.993

67

1.000

 

 

0.486

 

0.747

1.000

1.030

1.245

1.481

*

*

1.000

1.000

70

1.035

 

 

 

0.583

0.842

0.873

1.090

1.327

1.552

*

1.003

1.030

75

1.105

 

 

 

 

 

0.552

0.584

0.811

1.057

1.290

1.510

1.008

1.088

* Sensible capacity equals total capacity (no latent capacity) at conditions shown as "*"

 

 

 

 

Rev.: 03/29/04

ARI/ISO/ASHRAE 13256-1 uses entering air conditions of Clg- 80.6°F DB/66.2°F WB and Htg- 68°F DB/59°F WB

 

 

 

18

Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05

Page 20
Image 20
Carrier GT-G, GT-S, GT-PX specifications Airflow Correction Factors, Entering Air Correction Factors