Indoor & Outdoor Split Geothermal Comfort Systems

Heating

HE

LWT = EWT - GPM x 500

HC

LAT = EAT + CFM x1.08

Cooling

LWT = EWT +

HR

 

 

 

 

LC = TC - SC

GPM x 500

 

 

LAT (DB) = EAT (DB) -

 

 

SC

 

S/T =

SC

CFM x1.08

TC

CFM

= airflow, cubic feet/minute

HWC

= Hot Water Generator (desuperheater)

EWT

= entering water temperature, ˚F

 

 

capacity, Mbtuh

GPM

= water flow in US gallons/minute

WPD

= Water coil pressure drop (psi & ft hd)

EAT

= entering air temperature, Fahrenheit

EER

=

Energy Efficiency Ratio

 

(dry bulb/wet bulb)

 

 

= BTU output/Watt input

HC

= air heating capacity, Mbtuh

COP

=

Coefficient of Performance

TC

= total cooling capacity, Mbtuh

 

 

= BTU output/BTU input

SC

= sensible cooling capacity, Mbtuh

LWT

= leaving water temperature, °F

KW

= total power unit input, KiloWatts

LAT

= leaving air temperature, °F

HR

= total heat of rejection, Mbtuh

LC

= latent cooling capacity, Mbtuh

HE

= total heat of extraction, Mbtuh

S/T

= sensible to total cooling ratio

 

 

 

 

 

GT-GS & GT-S Performance Correction Factors

 

Heating Corrections

 

 

 

 

 

Cooling Corrections

 

 

 

 

 

 

 

 

 

 

 

 

 

Sens Clg Cap Multiplier - Entering DB °F

 

 

 

Ent Air DB

Htg Cap

Power

Heat of

 

Ent Air

Total Clg

 

 

 

 

 

 

 

Power

Heat of

 

70

75

80

80.6

85

90

95

°F

 

 

 

Ext

 

WB °F

Cap

 

Rej

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

1.019

0.896

1.054

 

60

0.881

0.943

1.067

1.192

1.240

*

*

*

0.983

0.899

65

 

1.010

0.948

1.028

 

65

0.940

0.797

0.952

1.106

1.125

1.261

*

*

0.991

0.949

68

 

1.004

0.980

1.011

 

66.2

0.976

0.693

0.868

1.043

1.063

1.217

*

*

0.997

0.980

70

 

1.000

1.000

1.000

 

67

1.000

0.624

0.812

1.000

1.023

1.188

1.343

1.352

1.000

1.000

75

 

0.997

1.059

0.979

 

70

1.012

 

0.697

0.820

0.835

0.944

1.067

1.257

1.002

1.010

80

 

0.993

1.118

0.957

 

75

1.024

 

 

0.637

0.658

0.817

0.983

1.159

1.005

1.019

Rev. 5/2/00M

* Sensible capacity equals total capacity (no latent capacity) at conditions shown as "*"

ARI/ISO/ASHRAE 13256-1 uses entering air conditions of Clg- 80.6°F DB/66.2°F WB and Htg- 68°F DB/59°F WB

Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05

17

Page 19
Image 19
Carrier GT-PX specifications Cooling, GT-GS & GT-S Performance Correction Factors