GT-PX
-Automatically performs special leak tests on all joints.
-Conducts pressure tests.
-Performs highly detailed run test unparalleled in the HVAC industry.
-Automatically disables packaging for a “failed” unit.
-Creates computer database for future service analysis and diagnostics from run test results.
•Heavy gauge galvanized steel cabinets are epoxy powder coated for durable and
•All refrigerant brazing is done in a nitrogen atmosphere.
•All units are deep evacuated to less than 100 microns prior to refrigerant charging.
•All joints are both helium and halogen leak tested to insure annual leak rate of less than 1/4 ounce.
•Coaxial heat exchanger, refrigerant suction lines and all water lines are fully insulated to eliminate condensation problems in low temperature applications.
•Noise Reduction features include: double isolation mounted compressors, compressor springs, insulated compressor compartment, and interior cabinet insulation using 1/2” coated glass fiber.
•Safety features include: high pressure and loss of charge to protect the compressor; condensate overflow protection; low water temperature limit sensors to safeguard the coaxial heat exchanger and air coil; hot water high limit and low compressor discharge temperature switch provided to shut down the hot water generator when conditions dictate. Fault lockout enables emergency heat and prevents compressor operation until thermostat or circuit breaker has been reset.
Options & Accessories
•Optional hot water generator with internally mounted pump.
•Optional cupronickel coaxial heat exchanger.
•Electronic thermostat.
•Closed loop Flow Controller.
•Electronic
•Hose kits.
Advanced Unit Controls With
Easy Diagnostics And
Unit Protection Sentinel Functions
Puron® HFC 410A Refrigerant
6
Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05