FUNCTIONAL INPUTS

NOTES: ! The term "activation" means closing an input circuit (via a relay or switch), and may be momentary or continuous. Momentary activations are superceded by any command. Continuous activations are superceded only by an overriding command.

$Activating any command when gate is at the open limit stops the Reclose Timer. When the command (except Manual CLOSE and STOP) is cleared, the Reclose Timer is reset.

MANUAL INPUTS: OPEN, CLOSE, AND STOP (TB2)

MAN OPEN

Activation fully opens the gate. Continuous activation holds

 

gate open. MAN OPEN overrides Anti-Tail-gate (ATG), Reclose

 

Timer, and all controls but MAN STOP.

MAN CLOSE

Activation fully closes the gate. Continuous activation holds

 

gate closed. MAN CLOSE overrides all controls but MAN STOP,

 

MAN OPEN and FIRE.

MAN STOP

De-activation stops opening and closing gates. MAN STOP

 

overrides Reclose Timer and all other controls, manual or

 

automatic. If MAN STOP is disconnected from its COMMON,

 

no commands affect the gate.
ENTRY SYSTEM/FIRE SWITCH INPUTS (TB9)

CYCLE Reclose Timer OFF:

Alternate Action allows a single command to both open and close the gate. Activation opens the gate, which remains open until another command is received. A CYCLE command when the gate is fully open closes the gate. CYCLE also opens a closing gate. If Anti-Tailgating (ATG) is enabled, Alternate Action is disabled. With ATG enabled, the gate begins closing as soon as the INTERRUPT LOOP clears.

Reclose Timer ON:

 

Activation opens the gate, then the Reclose Timer closes the

 

gate. A CYCLE command also opens a closing gate, but will not

 

close a fully open gate if the Reclose Timer is enabled. If Anti-

 

Tailgating (ATG) is enabled, the gate closes as soon as the

 

INTERRUPT LOOP clears.

FIRE

Activation opens the gate. Continuous activation holds the gate

 

open. If the Reclose Timer is disabled and FIRE is deactivated,

 

the gate closes after 5 seconds. If Reclose Timer is enabled, when

 

FIRE is deacitvated, the Reclose Timer starts. FIRE overrides all

 

commands but Manual STOP.

EXIT LOOP/SHADOW LOOP DETECTOR INPUTS (TB10)

EXIT LOOP

Same as CYCLE, but does not close the gate when it is fully open.

SHADOW LOOP

Activation prevents the gate from opening or closing so the gate

 

won't hit a vehicle. If the gate is already moving, or if the gate is

 

not fully opened or closed, this input has no effect.