Chicago Pneumatic CS7000 Power Supply, Ground Fault Circuit Interrupter Gfci, DIP Switch Settings

Models: CS7000

1 46
Download 46 pages 1.65 Kb
Page 28
Image 28

6159939130 CS7000 Controller Hardware Overview Manual

DIP Switch Settings

DIP switch block SW1 is used to configure the SDLC address. These are binary encoded to provide addresses 1 through 32 (zero is not a valid address). For Ethernet this address should be set to 1.

DIP switch block SW2 is for special options. Position #1 can force the unit into the FLASH program mode. Position #2 configures the printer port for DaimlerChrysler Plant Floor Communication System (PFCS) formatting.

Power Supply

A 1.3A, 24V power supply provides power for external I/O use.

Ground Fault Circuit Interrupter (GFCI)

The GFCI is wired in series from the AC power input to the servo amplifier. It monitors both AC power leads to the servo amplifier, ensuring that current flowing in one lead is the same as the current flowing out the other lead. If, due to a ground fault, the GFCI detects a net difference in the AC power exceeding 30 milliamps (30mA or.030 Amps), it shuts off the AC power to the servo amplifier automatically.

Test

Switch in ON position

Figure 2-9.Ground Fault Circuit Interrupter

Page 2-12

39-30-41365

Page 28
Image 28
Chicago Pneumatic CS7000 manual Power Supply, Ground Fault Circuit Interrupter Gfci, DIP Switch Settings