94 Chapter 5
Planning for Installation and Operation Table 5.7 9900 Physical Specifications
Item 9960 Controller 9960 Disk Unit *6 9910 Subsystem
Dimension
(mm/in)
Width 750 mm / 29.5 in *1 600 mm / 23.6 in *1 700 mm / 29.5 in *1
Depth 800 mm / 31.5 in
Height 1,790 mm / 70.5 in
Floor Area
with no service clearance
0.6 sq meters / 6.5 sq feet
0.48 sq meters / 5.16 sq feet
0.56 sq meters / 6 sq feet
Floor Area
with service clearance
1.8 sq meters / 19.4 sq feet
1.44 sq meters / 15.5 sq feet
1.47 sq meters / 15.8 sq feet
Weight (kg/lb) 412 / 908 *2 480 / 1 058
*5 480 / 1058
*3 440 / 970
*4 525 / 1157
*7 506 / 1116
*8
Heat Output (kW) 1.46 *2 3.43
*5 2.32
*3 2.85
*4 3.1
*7 2.81
*8
Power Consumption (kVA) 1.57 *2 3.72
*5 2.41
*3 3.14
*4 3.34
*7 3.06
*8
Air Flow (m3/min.) 18
*2 *3 12
*4 *5 15
*7 *8
Notes:
*1. This includes the thickness of side covers (16 mm/0.6 in × 2).
*2. These values are used when 9960 has 8 GB cache memory, two fibre 8- port adapters, and an additional disk adapter.
*3. These values are used when 9960 Controller has maximum options.
*4. These values apply to a maximum size Disk Unit using 18-GB hard disk drives (HDDs).
*5. These values apply to a maximum size Disk Unit using 47-GB or 73-GB HDDs.
*6. The number of Disk Units per 9960 subsystem is 1-6.
*7. These values are used when 9910 has 16 GB cache, three fibre 8-port adapters, and fully populated with 47- or 73-GB HDDs.
*8. These values are used when 9910 has 16 GB cache memory, three fibre 8-port adapters, and fully populated with 18-GB HDDs.