108 Chapter 5
Planning for Installation and Operation
Table 5.13 Floor Load Rating for 9960 Controller with Maximum Configuration
Required clearance (a+b)
Clearance (C) in meters (feet)
Floor Load Rating
kg/m2 (lb/ft2) C = 0 C = 0.2 (0.66) C = 0.4 (1.31) C = 0.6 (1.97) C = 1.0 (3.28)
500 (102.4)
0.2 m (0.66 ft) 0 0 0 0
450 (92.2) 0.9 m (3 ft) 0.3 m (1 ft) 0 0 0
400 (81.9) 1.8 m (5.9 ft) 1.1 m (3.6 ft) 0.6 m (2 ft) 0.2 m (0.66 ft) 0
350 (71.7) 3.2 m (10.5 ft) 2.4 m (7.9 ft) 1.7 m (5.6 ft) 1.1 m (3.6 ft) 0.3 m (1 ft)
300 (61.4) 5.4 m (17.7 ft) 4.3 m (14.1 ft) 3.4 m (11.2 ft) 2.7 m (8.9 ft) 1.6 m (5.2 ft)