Hitachi Lightning 9900™ User and Reference Guide 105

5.5.3 Floor Load Rating

Figure 5.22, Figure 5.23, and Table 5.10 through Table 5.13 illustrate the floor loading

ratings for various 9960 and 9910 subsystem configurations.

Table 5.10 Floor Load Rating for 9910 Subsystem

Required Clearance (a+b)
Clearance (C) in meters (feet)
Floor Load Rating
kg/m2 (lb/ft2) C = 0 C = 0.2 (0.66) C = 0.4 (1.31) C = 0.6 (1.97) C = 1.0 (3.28)
500 (102.4) 0.6 m (2 ft) 0.3 m (1 ft) 0.1 m (.3 ft) 0 0
450 (92.2) 0.8 m (2.6 ft) 0.5 m (1.6 ft) 0.3 m (1 ft) 0.1 m (.3 ft) 0
400 (81.9) 1.0 m (3.3 ft) 0.7 m (2.3 ft) 0.5 m (1.6 ft) 0.3 m (1 ft) 0
350 (71.7) 1.4 m (4.6 ft) 1.0 m (3.3 ft) 0.7 m (2.3 ft) 0.5 m (1.6 ft) 0.2 m (0.66 ft)
300 (61.4) 2.0 m (6.6 ft) 1.5 m (4.9 ft) 1.1 m (3.6) 0.9 m (3 ft) 0.5 m (1.6 ft)

Table 5.11 Floor Load Rating for 9960 Controller with 1 Disk Array

Required Clearance (a+b)
Clearance (C) in meters (feet)
Floor Load Rating
kg/m2 (lb/ft2) C = 0 C = 0.2 (0.66) C = 0.4 (1.31) C = 0.6 (1.97) C = 1.0 (3.28)
500 (102.4) 0 0 0 0 0
450 (92.2) 0.2 m (0.66 ft) 0 0 0 0
400 (81.9) 0.5 m (1.6 ft) 0.3 m (1 ft) 0.1 m (.3 ft) 0 0
350 (71.7) 0.9 m (3 ft) 0.7 m (2.3 ft) 0.5 m (1.6 ft) 0.3 m (1 ft) 0
300 (61.4) 1.6 m (5.2 ft) 1.3 m (4.3 ft) 1.0 m (3.3 ft) 0.8 m (2.6 ft) 0.4 m (1.3 ft)