Continental CDIZC - P Adjustments, Pilot Burner Adjustment, Vent Restriction, Venturi Adjustment

Models: CDIZC - P CDIZC - N

1 16
Download 16 pages 31.53 Kb
Page 11
Image 11
ADJUSTMENTS

11

ADJUSTMENTS

PILOT BURNER ADJUSTMENT

Remove the pilot screw cap. Adjust the pilot screw to pro- vide properly sized flame. Turn in a clockwise direction to reduce the gas flow. Replace the pilot screw cap.

FIGURE 27

FIGURE 28

VENT RESTRICTION

Some vent configurations may display a very active flame. If this appearance is not desirable, the vent exit may be re- stricted using the restrictor plate shown in FIGURE 6b. Bend the flap up as shown to reduce the velocity of the exhaust gases, slowing down the flame pattern and creating a more traditional appearance.

VENTURI ADJUSTMENT

This unit is approved for use with a 2" liner for air intake and a 3" liner for exhaust. For best performance, however, it is recommended to use two 3" liners.

Air shutter settings will differ depending on the liner sys- tem used. Use the charts below to determine the correct air shutter setting:

 

3"/3"LINERSYSTEM

NG

1/16"

LP

3/16"

 

AIR SHUTTER SETTING

 

 

 

 

 

2"/3"LINERSYSTEM

NG

1/8"

LP

5/16"

 

AIR SHUTTER SETTING

Closing the air shutter will cause a more yellow flame, but can lead to carboning. Opening the air shutter will cause a more blue flame, but can cause flame lifting from the burner ports. The flame may not appear yellow immediately; allow 15 to 30 minutes for the final flame colour to be estab- lished.

Air shutter adjustment must only be done by a qualified gas installer!

FIGURE 30

HELPFUL HINT:

A mirror will let you see the opening of the air shutter without removing the burner. Scribe a line along the venturi tube and air shutter cap. Open or close according to the original opening by using the scribed line as your datum.

FIGURE 29

W415-0224 / D / 01.15.04

Page 11
Image 11
Continental CDIZC - P manual Adjustments, Pilot Burner Adjustment, Vent Restriction, Venturi Adjustment, 3/3LINERSYSTEM