Directional Antennas.

Directional antennas can be a:
• Yagi antenna with a main beam and orthogonal elements, or
• Directional radome, which is cylindrical in shape, or
• Parabolic antenna.
A directional antenna provides high gain in the forward direction, but lower
gain in other directions.This may be used to compensate for coaxial cable
loss for installations with marginal radio path.
Yagi antennas should be installed with the main beam horizontal,pointing
in the forward direction. If the Yagi is transmitting to a vertically mounted
omni-directional antenna, then the Yagi elements should be vertical.If the
Yagi is transmitting to another Yagi,then the elements at each end of the
wireless link need to in the same plane (horizontal or vertical).
Directional radomes should be installed with the central beam horizontal
and must be pointed exactly in the direction of transmission to benefit from
the gain of the antenna. Parabolic antennas should be mounted as per the
manufacturer’s instructions,with the parabolic grid at the “back” and the
radiating element pointing in the direction of the transmission.
Ensure that the antenna mounting bracket is well connected to
“ground/earth.”
2.2 Power Supply
The BU-245U-E module can be powered from a 9 - 30Vdc power supply.
The power supply should be rated at 1 Amp.The positive side of the
supply must not be connected to earth.The supply negative is connected
to the unit case internally.The DC supply may be a floating supply or
negatively grounded.
The power requirements of the BU-245U-E unit are shown in the
following table.
BU-245U-E-G BU-245U-E-A
12Vdc 24Vdc 12Vdc 24Vdc
Quiescent 290mA 150mA 300mA 160mA
TX @100mW 310mA 170mA 370mA 190mA
TX @ 400mW 340mA 180mA 410mA 210mA
A Ground Terminal is provided on the back of the module.This Terminal should be connected to the Main Ground point of the installation in order
to provide efficient surge protection for the module (refer to the Installation Diagram).
3A1576Rev1.6