16 www.cooperbussmann.com/BussmannWirelessResources
Cooper Bussmann BU-245U-E Wireless Ethernet & Device Server User Manual
Shorter runs of 485 cable may not require the termination resistors to be enabled.
2.4 Discrete (Digital) Input/Output
The BU-245U-E has one on-board discrete/digital I/O channel.This channel can act as either a discrete input or discrete output. It can be
monitored, or set remotely,or alternatively used to output a communications alarm status.
If used as an “input”,the I/O channel is suitable for voltage free contacts (such as mechanical switches) or NPN transistor devices (such as
electronic proximity switches). PNP transistor devices are not suitable.Contact wetting current of approximately 5mA is provided to maintain
reliable operation of driving relays.
The digital input is connected between the "DIO" terminal and common “COM.”The I/O circuit includes a LED indicator which is lit GREEN when
the digital input is active, that is,when the input circuit is closed. Provided the resistance of the switching device is less than 200 ohms, the
device will be able to activate the digital input.
The I/O channel may also be used as a discrete output.The digital outputs are transistor switched DC signals, FET output to common rated at
30Vdc 500mA.
The output circuit is connected to the "DIO" terminal. The digital output circuit includes a LED indicator which is lit RED when the
digital output is active.
3A1576Rev1.6