3.25 Remote Configuration
Because a module configuration is viewed and changed in a web format (which uses TCP/IP protocol),you can view or change the configuration of
a remote module via the wireless link, provided the remote module already have a wireless link established to the local BU-245U-E.
To perform remote configuration,connect a PC to the local module, run Internet Explorer and enter the IP address of the remote unit (or device
name if using DNS) - the configuration page of the remote module will be shown and changes can be made.
Care must be taken if modifying the configuration of a module remotely.If the Radio Configuration is changed, some changes made may
cause loss of the radio link, and therefore the network connection.
It is advisable to determine the path of the links to the modules you wish to modify,and draw a tree diagram if necessary. Modify the modules at
the “leaves”of your tree diagram. These will be the furthest away from your connection point in terms of the number of radio or Ethernet links.
In a simple system, this usually means modifying the Client modules first and the Access Point last.
Remote Configuration Priority
3.26 Configuration Examples

Setting a BU-245U-E to Factory Default Settings

Access configuration webpage on the BU-245U-E. Refer section”3.2.”
• Click on “System Tools”Menu Item
• Click on Factory Default Configuration Reset, and wait for unit to reset.
While the module executes the reset sequence the OK LED will flash.
The OK LED will turn green when the reset sequence is complete.